| Plan Review Notes For Permit 03050148 |
| Permit Number |
03050148 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-12-12 00:00:00 | 1) FIRE SPRINKLERS SHALL BE INSTALLED | | | IN ELECTRIC AND CABLE TV CLOSETS. | | | | | | 2) FDC SHALL BE 2 1/2" NOT 1 1/2" AS | | | SHOWN FOR BUILDINGS 1 AND 2 FDC DETAIL | | | SHOWN ON FP-2. | | | | | | 3) THE FLOW TEST NOTED WITH PLANS | | | IS OVER ONE YEAR OLD. 11.7.02. | | | | | | 4) BREEZEWAY WALLS ARE TWO HOUR FIRE | | | RATED WITH C LABEL FIRE DOORS. PLEASE | | | EXPLAIN RATIONALE. | | | | | | 5) THE BUILDING PLAN REVIEWER NOTED | | | SOME MISSING PAGES TO THE PLANS. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|