2004-02-25 00:00:00PROVISO:
 THE FOLLOWING ITEMS HAVE CHANGED WITH
 THE REVISED 2001 FBC(M), EFFECTIVE JUNE
 30, 2003:
  
 1.PER 2001 FBC(M) 403.3, VENTILATION
 SYSTEMS OTHER THAN R-3 (ONE/TWO FAMILY),
 SHALL HAVE THE MINIMUM REQUIREMENTS OF
 OUTSIDE AIR IN ACCORDANCE WITH TABLE
 403.3. PLEASE REVISE PLANS TO REFLECT
 THIS REQUIREMENT.
  
 2.AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001 FBC(M)
 307.2.3.
  