2004-02-28 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
  
 1.)PROVIDE A SURVEY FOR THIS PARCEL.
  
 2.)PROVIDE A DIMENSIONED SITE PLAN.
  
 3.)ZONING APPROVAL REQUIRED BEFORE
 PERMIT ISSUANCE.
  
 4.)THE WINDOW SIZES EXCEED THE MAXIMUM
 SIZE ALLOWED BY THE SBCCI TEST REPORTS,
 WHICH IS APPARENTLY WHY ENGINEERING FOR
 THE WINDOWS WAS SUBMITTED.HOWEVER, ANY
 ENGINEERING SUBMITTED IN LIEU OF TEST
 REPORTS MUST BE ORIGINAL AND SEALED IN
 ACCORDANCE WITH FS471.025, WITH
 THE INFORMATION REQUIRED TO BE ON EACH
 SHEET AS PER FAC61G-23.002.ALSO, THE
 SITE SPECIFIC PAPERWORK INDICATES A
 LIMITATION OF +30/-30 FOR DESIGN
 PRESSURE; SEE SHEET A-DT1 FOR DESIGN
 LOAD REQUIREMENTS.
  
 5.)THE PRODUCT APPROVALS SUBMITTED FOR
 THE IMPACT FRENCH DOORS ARE FOR SMALL
 MISSILE IMPACT ONLY.SHUTTERS WOULD
 BE REQUIRED BELOW 30'.IMPACT
 PROTECTION IS TO BE FOR LARGE MISSILE
 IMPACT, FBC1606.1.4(1).
  
 6.)SITE SPECIFIC PRODUCT APPROVALS ARE
 TO BE SEALED IN TWO PLACES; ENGINEER AND
 DESIGNER OF RECORD.
  
 7.)FOR THE NON-IMPACT FRENCH DOOR,
 CLEARLY INDICATE ON DRAWING W03-38 WHICH
 DESIGN YOU ARE USING AS NOT ALL MEET
 DESIGN LOAD REQUIREMENTS.
  
 8.)SHEET 3 PREPARED BY AL-FAROOQ
 CORPORATION FOR THE WINDOWS INDICATES
 THAT 1ST & 2ND FLOOR WILL HAVE NON-
 IMPACT WINDOWS.IMPACT REQUIRED ON THE
 2ND FLOOR AS PER YOUR APPROVED PLAN.
 ALSO APPLIES TO SHEETS 7, 11.
  
 9.)SHEET 4 IS FOR A SINGLE HUNG WINDOW
 BUT INDICATES THAT IT IS FOR MARK C,
 WHICH IS A FIXED WINDOW.NOTE THAT THIS
 WINDOW DOES NOT REQUIRE ENGINEERING AS
 IT IS COVERED UNDER THE SUBMITTED
 SBCCI TEST REPORT. (AL-FAROOQ)
  
 10.)SHEET 5 INDICATES THAT IMPACT IS
 FOR THE 3RD FLOOR, PLEASE NOTE THAT IT
 SHOULD BE FOR 2ND AND 3RD FLOOR (AL-
 FAROOQ).ALSO APPLIES TO SHEETS 9.
  
 11.)SHEET 12, MAX DESIGN PRESSURE IS
 -44.5 FOR THE HORIZONTAL ROLLER, NON-
 IMPACT.THIS DOES NOT MEET DESIGN
 PRESSURE REQUIREMENTS FOR ZONE 5.THE
 COVER SHEET INDICATES THAT ALL WINDOWS
 USE WORST CASE ZONE 5 (NOTE 4). ADDRESS.
  
 12.)SHEET 12 SHOWS A HORIZONTAL ROLLER
 WINDOW SIZE OF 72X54, THE CALCS ON
 SHEET 13 ARE FOR THIS SIZE, BUT THE PLAN
 SHOWS A SIZE OF 74X62.ALSO APPLIES TO
 SHEET 14 (IMPACT HORIZ.ROLLER). ADDRESS.
  
 13.)PRODUCT APPROVAL SUBMITTAL FORM
 FOR THE SINGLE HUNG WINDOW SHOWS A
 DESIGN PRESSURE OF +/- 950.IS THIS
 CORRECT?
  
 14.)ON THE SBCCI REPORT FOR THE
 SHUTTERS CLEARLY INDICATE THE PRODUCT
 TO BE INSTALLED AND CIRCLE ANCHORING
 TO BE USED.NOT ALL PRODUCTS MEET
 MINIMUM DESIGN CRITERIA.
  
 15.)PANELMATE ANCHORS ARE INDICATED ON
 THE SHUTTER INSTALLATION SCHEDULE AND
 21-ADT5.THIS ANCHOR IS FOR CONCRETE/
 HOLLOW BLOCK INSTALLATIONS, SEE TEST
 REPORT.
  
 16.)PRODUCT APPROVALS FOR THE LOUVERED
 DOORS WERE NOT SUBMITTED.
  
 17.)JAMERCO DATA (MISC HARDWARE
 SECTION OF THE PRODUCT APPROVAL BOOK)
 IS ILLEGIBLE.THE PLAN NOTES JAMERCO
 .143"X 1 1/2" PINS, BUT THE SEMCO
 CONNECTORS WERE TESTED WITH .145"
 POWER FASTENERS.SUBMIT LEGIBLE
 PAPERWORK AND HAVE THE ENGINEER
 ADDRESS.
  
 18.)SUBMIT REVISED PRODUCT APPROVAL
 PAPERWORK FOR THE OTHER BUILDINGS IF
 NECESSARY.