Plan Review Notes
Plan Review Notes For Permit 03050145
Permit Number 03050145
Review Stop P
Sequence Number 1
Notes
Date Text
2003-12-16 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FLA. ADMIN. CODE
 FLA. STATUTES
  
 1) SHTS P-U1 THRU P-U4 WATER RISER DIA-
 GRAMS, A WATER HAMMER ARRESTOR IS REQ-
 UIRD FOR THE ICE MAKER LINE TO THE REF-
 RIDGERATOR. (NOT IN CEILING - PDI-WH 201
 AND MANUF. INSTALL. INSTRUCT. 604.9).
 2) SHT P-T1.3 THERMAL EXPANSION CONTROL
 NOT PROPERLY ADDRESSED WITH THE 3/4"
 VALVE AT THE BACKFLOW. 607.3.2
 3) ENGINEERS SHALL SUBMIT SIGNATURE ON
 SEAL. FAC 61G15-23.002(1) & FS 471.025.
 INITALS ARE NOT ACCEPTABLE PER FBPE AND
 BLDG OFFICIAL.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]