| 2003-12-16 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FLA. ADMIN. CODE | | | FLA. STATUTES | | | | | | 1) SHTS P-U1 THRU P-U4 WATER RISER DIA- | | | GRAMS, A WATER HAMMER ARRESTOR IS REQ- | | | UIRD FOR THE ICE MAKER LINE TO THE REF- | | | RIDGERATOR. (NOT IN CEILING - PDI-WH 201 | | | AND MANUF. INSTALL. INSTRUCT. 604.9). | | | 2) SHT P-T1.3 THERMAL EXPANSION CONTROL | | | NOT PROPERLY ADDRESSED WITH THE 3/4" | | | VALVE AT THE BACKFLOW. 607.3.2 | | | 3) ENGINEERS SHALL SUBMIT SIGNATURE ON | | | SEAL. FAC 61G15-23.002(1) & FS 471.025. | | | INITALS ARE NOT ACCEPTABLE PER FBPE AND | | | BLDG OFFICIAL. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|