| Plan Review Notes For Permit 03050145 |
| Permit Number |
03050145 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-12-12 00:00:00 | APPROVED PROVISO: | | | | | | 1) FIRE SPRINKLER HEADS SHALL NOT BE | | | DELETED FROM ELECTRIC AND CABLE ROOMS. | | | | | | 2) THE FIRE DEPARTMENT CONNECTIONS SHALL | | | BE 2 1/2 INCH NOT 1 1/2 INCH AS SHOWN | | | IN FDC DETAIL ON PAGE FP-2. | | | | | | 3) POST INDICATOR VALVES ARE REQUIRED. | | | | | | 4) PLEASE EXPLAIN THE TWO HOUR BREEZEWAY | | | WALLS WITH C LABELED FIRE DOORS. PLEASE | | | EXPLAIN RATIONALE. | | | | | | 5) THE DATE OF THE FLOW TEST IS OVER | | | ONE YEAR OLD. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|