Plan Review Notes
Plan Review Notes For Permit 03050145
Permit Number 03050145
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2003-12-12 00:00:00APPROVED PROVISO:
  
 1) FIRE SPRINKLER HEADS SHALL NOT BE
 DELETED FROM ELECTRIC AND CABLE ROOMS.
  
 2) THE FIRE DEPARTMENT CONNECTIONS SHALL
 BE 2 1/2 INCH NOT 1 1/2 INCH AS SHOWN
 IN FDC DETAIL ON PAGE FP-2.
  
 3) POST INDICATOR VALVES ARE REQUIRED.
  
 4) PLEASE EXPLAIN THE TWO HOUR BREEZEWAY
 WALLS WITH C LABELED FIRE DOORS. PLEASE
 EXPLAIN RATIONALE.
  
 5) THE DATE OF THE FLOW TEST IS OVER
 ONE YEAR OLD.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910