| 2003-12-31 00:00:00 | ****CORRECTIONS***** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | [email protected] |
| | |
| | 1.)A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2.)IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY.THE PLANS MUST BE |
| | STAMPED AND THE RECEIPT ATTACHED TO THE |
| | APPLICATION. |
| | |
| | 3.)NOTE THAT THIS PROJECT HAS FAILED |
| | ZONING.A PERMIT CANNOT BE ISSUED |
| | WITHOUT ZONING APPROVAL. |
| | |
| | 4.)PROVIDE A SOILS INVESTIGATION |
| | REPORT. |
| | |
| | 5.)SUBMIT PRODUCT APPROVALS FOR: |
| | INSWING DOOR |
| | 3068 OUTSWING DOOR |
| | FRENCH DOOR |
| | 6050 SLIDER, IMPACT AND NONIMPACT |
| | ROOF TILE |
| | HORIZONTAL ROLLER, IMPACT AND NONIMPAC |
| | SINGLE HUNG, IMPACT AND NONIMPACT |
| | SHUTTERS |
| | DOUBLE 3668 LOUVERED DOORS |
| | MODIFIED BITUMEN ROOF |
| | ANY OTHER PRODUCTS WHICH REQUIRE |
| | PRODUCT APPROVAL BUT ARE NOT LISTED. |
| | |
| | 6.)PROVIDE A FIREBLOCK DETAIL FOR THE |
| | SOFFIT FBC705.3. |
| | |
| | 7.)PROVIDE THE INSTALLATION PLAN FOR |
| | HURRICANE PROTECTION AS DISCUSSED.SEE |
| | A-DT1, SHUTTER NOTE, "THE OWNER WILL |
| | SUBMIT A 'PLAN OF ACTION' FOR THE |
| | INSTALLATION OF THE GROUND FLOOR |
| | SHUTTERS . . ."SUBMIT THIS PLAN FOR |
| | ALL OF THE BUILDINGS. |
| | PROVIDE AN INSTALLATION SCHEDULE, SEE |
| | ATTACHED. |
| | |
| | 8.)THERE ARE SEVERAL DETAILS ON THE |
| | PLAN WHICH REFER TO SEMCO CONNECTORS. |
| | SEMCO HAS BEEN OUT OF BUSINESS FOR OVER |
| | TWO YEARS.REVISE ALL AFFECTED DETAILS, |
| | FOR INSTANCE, AT1.4 TYPE "A" ROOF TIE |
| | DOWN DETAIL, HURRICANE STRAP/CONN NOTE |
| | 3, A-ADT3, B-ADT3.CHECK ALL DETAILS. |
| | |
| | 9.)STUCCO OVER WIRE LATH IN A VERTICAL |
| | APPLICATION IS REQUIRED TO BE 3 COAT |
| | 7/8" MIN, FBC2504.2.2, ASTM C926 (SEE |
| | ATTACHED).THE THICKNESS 5/8" APPEARS |
| | IN SEVERAL DETAILS, SUCH AS A-DT3. CHECK |
| | ALL DETAILS. |
| | |
| | 10.)THE ENTRY DOORS IN THE BREEZEWAY |
| | ARE TO BE 90 MINUTE TO COMPLY WITH THE |
| | 2 HR WALL REQUIREMENT, FBC TABLE |
| | 705.1.2.REVISE ALL AFFECTED DETAILS |
| | AND DOOR SCHEDULE. |
| | |
| | 11.)PROVIDE FIRE RATING INFORMATION |
| | FOR THE DOORS. |
| | |
| | 12.) SPECIAL INSPECTOR REQUIRED, FS |
| | 553.71(7).PROVIDE THE INSPECTION PLAN. |