2003-12-31 00:00:00****CORRECTIONS*****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE
 STAMPED AND THE RECEIPT ATTACHED TO THE
 APPLICATION.
  
 3.)NOTE THAT THIS PROJECT HAS FAILED
 ZONING.A PERMIT CANNOT BE ISSUED
 WITHOUT ZONING APPROVAL.
  
 4.)PROVIDE A SOILS INVESTIGATION
 REPORT.
  
 5.)SUBMIT PRODUCT APPROVALS FOR:
 INSWING DOOR
 3068 OUTSWING DOOR
 FRENCH DOOR
 6050 SLIDER, IMPACT AND NONIMPACT
 ROOF TILE
 HORIZONTAL ROLLER, IMPACT AND NONIMPAC
 SINGLE HUNG, IMPACT AND NONIMPACT
 SHUTTERS
 DOUBLE 3668 LOUVERED DOORS
 MODIFIED BITUMEN ROOF
 ANY OTHER PRODUCTS WHICH REQUIRE
 PRODUCT APPROVAL BUT ARE NOT LISTED.
  
 6.)PROVIDE A FIREBLOCK DETAIL FOR THE
 SOFFIT FBC705.3.
  
 7.)PROVIDE THE INSTALLATION PLAN FOR
 HURRICANE PROTECTION AS DISCUSSED.SEE
 A-DT1, SHUTTER NOTE, "THE OWNER WILL
 SUBMIT A 'PLAN OF ACTION' FOR THE
 INSTALLATION OF THE GROUND FLOOR
 SHUTTERS . . ."SUBMIT THIS PLAN FOR
 ALL OF THE BUILDINGS.
 PROVIDE AN INSTALLATION SCHEDULE, SEE
 ATTACHED.
  
 8.)THERE ARE SEVERAL DETAILS ON THE
 PLAN WHICH REFER TO SEMCO CONNECTORS.
 SEMCO HAS BEEN OUT OF BUSINESS FOR OVER
 TWO YEARS.REVISE ALL AFFECTED DETAILS,
 FOR INSTANCE, AT1.4 TYPE "A" ROOF TIE
 DOWN DETAIL, HURRICANE STRAP/CONN NOTE
 3, A-ADT3, B-ADT3.CHECK ALL DETAILS.
  
 9.)STUCCO OVER WIRE LATH IN A VERTICAL
 APPLICATION IS REQUIRED TO BE 3 COAT
 7/8" MIN, FBC2504.2.2, ASTM C926 (SEE
 ATTACHED).THE THICKNESS 5/8" APPEARS
 IN SEVERAL DETAILS, SUCH AS A-DT3. CHECK
 ALL DETAILS.
  
 10.)THE ENTRY DOORS IN THE BREEZEWAY
 ARE TO BE 90 MINUTE TO COMPLY WITH THE
 2 HR WALL REQUIREMENT, FBC TABLE
 705.1.2.REVISE ALL AFFECTED DETAILS
 AND DOOR SCHEDULE.
  
 11.)PROVIDE FIRE RATING INFORMATION
 FOR THE DOORS.
  
 12.) SPECIAL INSPECTOR REQUIRED, FS
 553.71(7).PROVIDE THE INSPECTION PLAN.