2003-06-23 00:00:00*********** NOTES REDLINED ***********
  
 1)NOTE: PLEASE SEE CONDUCTOR SIZE AND
 OCP FOR 10KW HEATSTRIP. SHOWS 40A AND #8
 ON PANEL SCHEDULE AND SHOWS 60A #8 ON
 LOAD CALCAULTIONS.
 SIZE PER 424-3 60A #6`S.
  
 2)NOTE: PLEASE SEE OCP SHOWN FOR WASHER
 ON LOAD CALCULATIONS. SHOWS 30A OCP FOR
 #12. (MISPRINT).
  
  
 PLEASE SEE THAT THE ABOVE IS REDLINED
 ON PLANS AND NO CORRECTIONS ARE NEEDED
 AT THIS TIME.