Plan Review Notes
Plan Review Notes For Permit 03050126
Permit Number 03050126
Review Stop E
Sequence Number 1
Notes
Date Text
2003-05-17 00:00:00*************** UNSAT *************
  
 1)NOTE: PLEASE SEE FS/ FAC 61G15-23.002
 ALL PLANS SIGNED AND SEALED BY AN ENG
 MUST CONTAIN A TITLE BLOCK CONTAINING
 ALL INFORMATION AS REQ`D IN ABOVE FS.
 NAME, ADDRESS, LICENSE #, ETC
  
 2)NOTE: SERVICE ENTRANCE CONDUCTORSNOT
 RATED FOR 225A. PLEASE SEE 310-15(B)6
 FOR MIN SEC`S.
 PLEASE ALSO SEE FOR NEUTRAL COND. SIZE.
  
 3)NOTE: PLEASE SEE LOAD CALCUALTIONS FOR
 A/C SYSTEMS. PLEASE SEE MULTIPLE LOADS
 SHOWN AND REPEATED. PLEASE SHOW AS SET
 FORTH IN NEC 220.
 PLEASE VERIFY SIZE OF HEAT FOR 6KW UNITS
 IF UNITS ARE 6W? < THEN PLEASE SIZE
 CONDUCTORS AND OCP PER 310-16 AND 424-3B
 MIN 125%.
  
 4)NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) ON PANEL SCHEDULE PER 210-52D
 210-11C3
  
 5)NOTE: PLEASE LIST THE REQ`D ARC FAULT
 CIRCUITS ON PANEL SCHEDULE PER 210-12.
  
 6)NOTE: PLEASE SUBMIT/SHOW AIC RATING
 FOR MAIN. AIC RATINGS ARE SHOWN FOR
 BRANCH BRKRS. 110-9/215-5
  
 7)NOTE: PLEASE SHOW ALL REQ`D GFI/GFI
 PROTECTED RECEPTS. 210-8/ 210-8A6
 KITCHEN, GARAGE/ OUTSIDE, BATH(S) ,
 LAUNDRY RM.
 8)NOTE: PLEASE SEE MISSING SD REQ`D ON
 SECOND FLR NFPA-72 8-1.4.2 ON FIRST FLR
 IN IMMEDIATE VICINITY OF STAIRS LEADING
 TO FLR ABOVE.
  
 9)NOTE:PLEASE CLARIFY RECEPT SHOWN ON
 STAIRS? MISPRINT
  
 10)NOTE: PLEASE SHOW SERVICE/PANEL ON
 PLANS.(LOCATION)
  
 11)NOTE: PLEASE SHOW EITHER, ELEC HOOK-
 -UP OR DISC FOR WATER HEATER, DEPENDING
 ON LOCATION OF PANEL?
  
 12)NOTE: PLEASE SHOW ALL A/C EQUIPMENT
 ON ELEC PLANS. DISC`S, REQ`D RECEPT?
 440-11
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. PLEASE TAKE OUT ALL OLD/VOIDED
 SHEETS AND INSERT NEW SHEETS INTOTWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE ALSO SEE G-1/G-2 SIGNATURE FOR
 ENG MUST BE ORIG SIG. PER FS 471.025
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]