| Plan Review Notes For Permit 03050122 |
| Permit Number |
03050122 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2003-07-12 00:00:00 | *****CORRECTIONS****** | | | | | | 1.)MECHANICAL WORK WAS ADDED TO THE | | | PLAN IN INK.ALL CHANGES TO A SEALED | | | DRAWING MUST BE INITALED AND DATED BY | | | THE ENGINEER. | | | | | | 2.)SIGN THE OWNER/AGENT LINE OF THE | | | ENERGY CALC. | | | | | | 3.)FIRESTOP REQUIRED, FBC 705.3. | | | | | | 4.)INSULATION WAS PUT ON THE PLAN | | | WITH WHITE OUT.ALL CHANGES TO THE | | | PLAN MUST BE INITIALED AND DATED BY | | | THE ENGINEER. | | | | | | 5.)THE CONNECTION SPECIFIED FROM THE | | | TIE BEAM TO THE WOOD BEAM SPECIFIES | | | 16-10DX1.ACCORDING TO THE SIMPSON | | | 2003 CATALOG, THE NAIL LENGTH IS | | | REQUIRED TO BE 1 1/2. | | | | | | 6.)SEE THE PREVIOUS CORRECTION LIST, | | | #7.GIVE EXISTING ATTACHMENTS WITH | | | UPLIFT INFORMATION. | | | | | | 7.)THE INTERNAL PRESSURE COEFFICIENT | | | IN THE WIND INFORMATION SECTION OF THE | | | PLAN IS INCORRECT.A COEFFICIENT IS | | | A NUMBER. | | | | | | 8.)THE ROOF TRUSS LOAD (WIND | | | INFORMATION) STATES "PER TRUSS | | | ENGINEERING".THERE AREN'T ANY | | | TRUSSES IN THIS DESIGN. | | | | | | SAMANTHA THYNG, BUILDING PLANS EXAMINER | | | [email protected] |
|