Plan Review Notes
Plan Review Notes For Permit 03050122
Permit Number 03050122
Review Stop B
Sequence Number 3
Notes
Date Text
2003-07-12 00:00:00*****CORRECTIONS******
  
 1.)MECHANICAL WORK WAS ADDED TO THE
 PLAN IN INK.ALL CHANGES TO A SEALED
 DRAWING MUST BE INITALED AND DATED BY
 THE ENGINEER.
  
 2.)SIGN THE OWNER/AGENT LINE OF THE
 ENERGY CALC.
  
 3.)FIRESTOP REQUIRED, FBC 705.3.
  
 4.)INSULATION WAS PUT ON THE PLAN
 WITH WHITE OUT.ALL CHANGES TO THE
 PLAN MUST BE INITIALED AND DATED BY
 THE ENGINEER.
  
 5.)THE CONNECTION SPECIFIED FROM THE
 TIE BEAM TO THE WOOD BEAM SPECIFIES
 16-10DX1.ACCORDING TO THE SIMPSON
 2003 CATALOG, THE NAIL LENGTH IS
 REQUIRED TO BE 1 1/2.
  
 6.)SEE THE PREVIOUS CORRECTION LIST,
 #7.GIVE EXISTING ATTACHMENTS WITH
 UPLIFT INFORMATION.
  
 7.)THE INTERNAL PRESSURE COEFFICIENT
 IN THE WIND INFORMATION SECTION OF THE
 PLAN IS INCORRECT.A COEFFICIENT IS
 A NUMBER.
  
 8.)THE ROOF TRUSS LOAD (WIND
 INFORMATION) STATES "PER TRUSS
 ENGINEERING".THERE AREN'T ANY
 TRUSSES IN THIS DESIGN.
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER