| 2003-05-23 00:00:00 | ******CORRECTIONS****** |
| | |
| | SAMANTHA THYNG, BUILDING PLANS EXAMINER |
| | [email protected] |
| | |
| | 1.)A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2.)IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY.THE PLANS MUST BE |
| | STAMPED AND THE ORIGINAL RECEIPT |
| | ATTACHED TO THE APPLICATION.233-5025 |
| | |
| | 3.)SEPARATE PERMITS REQUIRED. |
| | |
| | 4.)ADDITIONAL FEES REQUIRED. |
| | |
| | 5.)ENERGY CALCS REQUIRED FBC 13-101.2. |
| | |
| | 6.)SPECIFY INSULATION. |
| | |
| | 7.)HOW WILL THE WALL SECTION BE |
| | STRUCTURALLY CONTINUOUS?NO ATTACHMENTS |
| | ARE SHOWN.GIVE EXISTING ATTACHMENTS |
| | WITH UPLIFT INFORMATION, AND PROPOSED |
| | ATTACHMENTS.IS THE WOOD BEAM PRESSURE |
| | TREATED?HOW WILL THE TIE BEAM UNDER |
| | THE WOOD BEAM, WITH NO WEIGHT BEARING |
| | ON THE TIE BEAM, BE STRUCTURALLY |
| | CONTINUOUS? |
| | |
| | 8.)SEMCO ATTACHMENTS ARE NOT |
| | AVAILABLE.SPECIFY ANOTHER BRAND WITH |
| | UPLIFT.ALL ATTACHMENTS SHOWN SHOULD |
| | SHOW UPLIFT. |
| | |
| | 9.)SHOW THE 12" BELOW GRADE, 4" ABOVE |
| | GRADE FOR THE FOUNDATION REQUIRED BY |
| | CODE ON THE WALL SECTION, FBC1804.1.3. |
| | |
| | 10.) GIVE A SOFFIT VENT SCHEDULE. |
| | CANNOT "MATCH EXISTING" AS THE EXISTING |
| | MIGHT NOT COMPLY WITH FBC 2309.7. |
| | |
| | 11.) SUBMIT PRODUCT APPROVALS FOR |
| | THE SINGLE HUNG WINDOWS, IMPACT |
| | PROTECTION, AND THE DOOR (2 LEGIBLE |
| | COPIES EACH). |