| Plan Review Notes For Permit 03050107 |
| Permit Number |
03050107 |
|
| Review Stop |
P |
| Sequence Number |
8 |
|
| Notes |
| Date |
Text |
| 2004-12-13 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | | | | 1) SHT P1.02 SANITARY LINE FROM HUB | | | DRAINS FOR FIRE LINE DRAINS SHOWS | | | DIRECTION OF FLOW IN TWO DIRECTIONS NEAR | | | THE AIR INTAKE WELL. PLEASE CLARIFY. | | | SECTION 104.2.1 | | | 2) SHT P3.09 ACCUMULATED SQUARE FOOTAGE | | | IN THE STORM SYSTEM IS NOT CORRECT. SEE | | | AREA BY REVISION #3, 12" (20205) PLUS | | | FORCED MAIN FROM BELOW (6900) SHOULD BE | | | TOTAL OF 27105 SQ.FT., BUT PLANS SHOW | | | 39385 SQ.FT. SECTION 104.2.1 | | | 3) SHT P3.09 PIPING AT RISER "C" SHOWS | | | 10" PIPE (9650), AND 8" (7960). 8" | | | SHOULD READ (5380) AND 10" SHOULD READ | | | (12980). SECTION 104.2.1. | | | 4) SHT P3.10 FROM PREVIOUS COMMENT, | | | PLEASE CORRECT THE SQ.FT. FROM RISER "C" | | | TO READ 12,980 SQ.FT. AND 22,440 | | | UPSTREAM OF THE STORM DRAIN LIFT | | | STATION. SECTOPM 104.2.1. | | | | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|