| 2005-08-09 00:00:00 | ********* UNSAT ********* |
| | |
| | REV'S FOR SHEETS E 2.01,2.03,2.04 |
| | |
| | 1)NOTE: PLEASE SEE SOME UNITS, SD'S |
| | SHALL BE INSTALLED WITHIN 3' OF THE PEAK |
| | OF A CEILING. PLEASE SEE AREAS IN UNITS |
| | WHERE SD'S ARE SHOWN ON "LOWERED" |
| | CEILING AREAS. |
| | NFPA-72 8-1.4 |
| | |
| | 2)NOTE: PLEASE SEE LT FIXTURES SHOWN |
| | ABOVE MASTER BATH/ BATH TUBS DOES NOT |
| | INDICATE ANY CIRCUITING, CONTROL ETC.? |
| | 215.5 |
| | |
| | 3)NOTE: PLEASE SEE 210.52C1 FOR KITCHEN |
| | COUNTERSPACE MIN RECEPT SPACING. |
| | UNIT B-2,A-1 MOD, PLEASE SEE ANY OTHER. |
| | 210.52C1-C5 |
| | |
| | 4)NOTE: PLEASE ADJUST "DINING/LIVING" |
| | RM/AREAS SHOWN ON MOST OF THE "A" UNITS. |
| | PLEASE SEE LIVING RM IS SHOWN WHERE |
| | DINING RM CIRCUITS ARE SHOWN AND DINING |
| | RM WHERE LIVING RM IS SHOWN. |
| | 215.5 |
| | |
| | ***PLEASE SEE THAT WHEN PLANS ARE |
| | SUBMITTED, PLEASE SUBMIT THREE COMPLETE |
| | SETS WITH ALL SHEETS INSERTED INTO SETS |
| | IN ORDER. A AND E SHEETS WERE PLACED IN |
| | ORDER AND INTO THREE SETS BY THIS OFFICE |
| | ON THIS SUBMITTAL. PLEASE BE SURE ALL |
| | FUTURE PLANS ARE DONE IN ORDER TO |
| | EXPEDITE THE PLAN REVIEW PROCESS AND |
| | AVOID ANY POSSIBLE DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REIVEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |