| Plan Review Notes For Permit 03050107 |
| Permit Number |
03050107 |
|
| Review Stop |
P |
| Sequence Number |
7 |
|
| Notes |
| Date |
Text |
| 2004-12-02 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | | | | 1) SHT P1.01 COL. LINE P.4/P.B INDICATES | | | THE PIPING TO (14) IS DELETED, BUT THE | | | RISER IS STILL SHOWN. PLEASE CLARIFY. | | | SECTION 104.2.1. | | | 2) STORM DRAIN LINE #9 BY ELEVATOR #1 BY | | | COL. LINE P.4. PLEASE INDICATE WHERE | | | THIS BRANCH LINE TIES INTO THE STACK. | | | SECTION 104.2.1. | | | 3) REVISIONS ON THE SANITARY SYSTEM | | | SHOWN ON SHT P1.01 SHALL BE REFLECTED ON | | | THE SANITARY RISER DIAGRAM. PLEASE | | | CORRELATE THE RISER DIAGRAM WITH THE | | | FLOOR PLAN. SECTION 104.2.1. | | | 4) SHT P1.01 SANITARY LINE BY THE | | | CLEANOUT NEAR COL.LINE P.5. PLEASE | | | INDICATE WHERE THIS LINE TIES INTO. | | | SECTION 104.2.1. | | | 5) SHT P3.10 THE STORM RISER DIAGRAM | | | DOES NOT REFLECT THE LAYOUT ON SHEET | | | P1.01. THE 3" PAD IS SHOWN CONNECTING | | | BETWEEN THE TRENCH DRAINS ON THE LAYOUT | | | SHEET, BUT DOWN STREAM OF BOTH TRENCH | | | DRAINS ON THE STORMDRAIN ISOMETRIC. | | | PLEASE CORRELATE THE RISER WITH THE | | | LAYOUT. SECTION 104.2.1 | | | | | | | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|