| Plan Review Notes For Permit 03050107 |
| Permit Number |
03050107 |
|
| Review Stop |
M |
| Sequence Number |
7 |
|
| Notes |
| Date |
Text |
| 2005-06-04 00:00:00 | 1 PAGE M1.01 CAN NOT TAKE AIR FRON | | | GARAGE TO PRESSUREISE STAIR TOWERS. | | | 2 PLEASE PROVIDE DOOR SCHEDULE PAGE A-48 | | | MISSING FROM PLANS.PLEASE PROVIDE TYPE | | | OF DOOR USED FOR A/C CLOSITS IN SUITES. | | | 3 PLEASE SHOWDETAIL ON PLANS FOR | | | RETURN AIR IN THE SUITES,FROM RETURN AIR | | | GRILL TO A/C. UNITS. | | | 4 PAGE M2.05 STUDIO 1 SHOWES BOOSTER FAN | | | IN DRYER EXHAUEST.REFER TO SECTION 504.6 | | | DOMESTIC CLOTHES DRYER DUCT,BOOSTER FANS | | | ARE NOT AN EXCEPTION. | | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|