| 2005-08-09 00:00:00 | ** UNSAT ** |
| | |
| | REV TO SHEET E1.11 AND LANSCAPE PLANS. |
| | |
| | PLEASE SEE SOME NOTES FROM PREVIOUS |
| | REVIEW. |
| | |
| | 1)NOTE: PLEASE PROVIDE ROOM DESIGNATIONS |
| | ON ROOF TOP PLANS. PLEASE SEE |
| | RESUBMITTED PLANS STILL DO NOT INDICATE |
| | ALL ROOMS? |
| | PLEASE SEE CIRCUITING AND LOCATIONS OF |
| | EQUIPMENT TO BE VERIFIED. |
| | PLEASE SEE THE FOLLOWING COMMENT.215.5 |
| | |
| | 2)NOTE: PLEASE SEE 620.23,620.24 FOR |
| | REQUIRED DEDICATED BRANCH CIRCUITS FOR |
| | EACH OF THE ELEVATOR MACHINE ROOMS. |
| | THESE CIRCUITS MAY NOT BE SHARED WITH |
| | OTHER AREAS AS SHOWN. |
| | |
| | 3)NOTE: PLEASE SEE680.22B, NO LIGHTING |
| | FIXTURES ARE PERMITTED WITHIN THE 5' |
| | EXTENDING OUTWARD FROM POOL'S WATER |
| | EDGE. PLEASE SEE LANDSCAPE PLANS ALSO. |
| | PLEASE ALSO SEE NO LOW VOLTAGE TYPE |
| | LIGHT FIXTURES ARE PERMITTED WITHIN 10' |
| | OF WATERS EDGE. THIS IS DUE TO NO |
| | EQUIPMENT GROUNDING IN LV TYPE FIXTURES |
| | AND LV SIDE OF TRANSFORMERS. |
| | 411.4 |
| | PLEASE SEE LANSCAPE LIGHTING FIXTURES. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |