| Plan Review Notes For Permit 03050107 |
| Permit Number |
03050107 |
|
| Review Stop |
M |
| Sequence Number |
6 |
|
| Notes |
| Date |
Text |
| 2005-03-01 00:00:00 | SUBMITTAL LETER DATED 2-7-05, RE: | | | BATHROOM & LAUNDRY EXHAUST | | | 1.DRYER BOOSTER FANS WILL HAVE TO BE | | | SUBMITTED UNDER "ALTERNATE MATERIALS AND | | | METHODS" PER 2001 FBC 103.7.1.PROVIDE | | | THE FOLLOWING DOCUMENTATION FOR REVIEW | | | BY NEIL MELICK, BUILDING OFFICAL: | | | 1.SUBMITTAL DATA/INSTALLATION | | | INSTRUCTIONS FOR THE DRYER. | | | | | | 2.SIGNED, SEALED AND DATED LETTER BY | | | THE ENGINEER FROM THE MANUFACTURER | | | INDICATING THAT THIS APPLICATION IS | | | APPROVED BY THE MANUFACTURER AND WILL | | | NOT VOID THE WARRANTY OF THE DRYER. | | | | | | 3.SUBMITTAL DATA/INSTALLATION | | | INSTRUCTIONS FOR THE BOOSTER FAN. | | | | | | CONCERNING THE ISSUE OF THE TERMINATION | | | OF THE BATHROOM AND LAUNDRY EXHAUST | | | TERMINATING ONTO THE BALCONY, THIS MUST | | | BE RESOLVED WITH HAROLD MOSER, CHIEF | | | MECHANICAL INSPECTOR AS I HAD APPROVED | | | THIS ON THE PLAN REVIEW. | | | |
|