| 2004-06-23 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 805 6716 |
| | E-MAIL: [email protected] |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | |
| | NOTE: |
| | THREE COPIES OF ARCHITECTURAL SHEETS |
| | A.02, A.03, A.35AND LS.5 WERE AMENDED, |
| | SIGNED AND DATED BY GUILLERMO ENCINOSA |
| | (ARCHITECT OF RECORD) BY HAND ON 6/23/04 |
| | |
| | FOR CONSISTENCY, THE FOLLOWING COMMENTS |
| | ARE NUMBERED AS PER THE BUILDING PLAN |
| | REVIEW OF 4/16/04: |
| | |
| | 1) THE COMMENT RESPONSE, DATED 5/8/04, |
| | IS NOTED. |
| | THE NOTICE OF COMMENCEMENT SHALL BE |
| | RECORDED AT PALM BEACH COUNTY COURTHOUSE |
| | AND A COPY SUBMITTED TO THIS OFFICE |
| | BEFORE A PERMIT CAN BE ISSUED.BLANK |
| | FORMS ARE AVAILABLE FROM THIS OFFICE. |
| | |
| | 2) THE COMMENT RESPONSE, DATED 5/8/04, |
| | IS NOTED. |
| | IMPACT FEES. THE PLANS SHALL BE TAKEN |
| | TO PALM BEACH COUNTY BUILDING DEPARTMENT |
| | FOR IMPACT FEE ASSESSMENT. THEY SHALL BE |
| | STAMPED AT THAT OFFICE AND A COPY OF THE |
| | PAID RECEIPT SUBMITTED TO THE CITY OF |
| | WEST PALM BEACH DEPT OF CONSTRUCTION |
| | SERVICES BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | 4) DECLARATION OF CONDOMINIUM BEFORE |
| | C.O. ISSUE.THE COMMENT RESPONSE, DATED |
| | 5/8/04 IS NOTED. |
| | |
| | 6) FBC* 105.13.1SPECIAL INSPECTOR. |
| | THIS COMMENT HAS NOT BEEN ADDRESSED. THE |
| | 'SPECIAL INSPECTOR AGREEMENT' WAS NOT |
| | RE-SUBMITTED.REPEATING THE COMMENTS |
| | FROM THE PREVIOUS REVIEW, THE SUBMITTED |
| | 'SPECIAL INSPECTOR AGREEMENT' IS MISSING |
| | THE LAST PAGE, WHICH IS TO BE SIGNED BY |
| | THE CONTRACTOR AND ARCHITECT/ENGINEER |
| | THE AGREEMENT SHALL ALSO BE SIGNEED BY T |
| | HE OWNER AND JOB INSPECTOR IN THE SPACE |
| | ALLOCATED.ALL SIGNATURES ARE TO BE |
| | NOTARIZED ORIGINALS. |
| | |
| | 7) SEPARATE SWIMMING POOL PERMIT APPLIC. |
| | THE COMMENT RESPONSE, DATED 5/8/04, IS |
| | NOTED. |
| | |
| | 9) FBC 13-103.1.2ENERGY CODE |
| | COMPLIANCE FORMS.THE COMMENT RESPONSE |
| | DATED 5/8/04, IS NOTED BUT SHEET 2 OF |
| | THE SUBMITTED ENERGY CODE COMPLIANCE |
| | FORMS SHALL BE SIGNED BY A KENCO |
| | COMMUNITIES REPRESENTATIVE AS 'OWNER', |
| | TO CERTIFY COMPLIANCE. |
| | |
| | 11) PRODUCT APPROVALS.THIS COMMENT HAS |
| | NOT BEEN PROPERLY ADDRESSED. |
| | NO PRODUCT APPROVALS HAVE BEEN SUBMITTED |
| | FOR THE ROOFING PRODUCTS, STOREFRONT AND |
| | HOLLOW METAL, LOUVERED, FLUSH (SINGLE |
| | AND DOUBLE AND ALUMINUM GLAZED SWING |
| | (SINGLE AND DOUBLE) EXTERIOR DOORS. |
| | |
| | 50) SHEET A.29PRE-CAST CONCRETE |
| | ARCHITECTURAL FEATURES/MOLDINGS.ONE |
| | OF THE THREE SETS OF PLANS STILL HAS |
| | THE 'OLD' REVISION OF SHEET A.29. INSERT |
| | THE LATEST REVISION AND REMOVE THE 'OLD' |
| | SHEET. |
| | |
| | 52) FBC 412.5(3)SHEET M4.01, SMOKE |
| | CONTROL NOTE C.THIS COMMENT HAS NOT |
| | BEEN PROPERLY ADDRESSED.THE REVISION |
| | MADE IS NOTED BUT THE NOTE C STILL DOES |
| | NOT MAKE SENSE AND DOES NOT CLEARLY |
| | EXPRESS THE ENGINEER'S INTENT.PLEASE |
| | READ THE NOTE AND CONSIDER THAT IT MAY |
| | BE CLARIFIED BY: |
| | - DELETING THE WORDS "..THROUGH THE..." |
| | FROM THE SECOND SENTENCE. |
| | - REPLACING THE WORDS "TO CLOSE AND..." |
| | WITH "IT SHALL ALSO..." AT THE BEGINNING |
| | OF THE LAST SENTENCE. |
| | |
| | 53) FBC 1005.6.9.9SHEET M4.01, SMOKE |
| | CONTROL NOTE 3B - STAIR BAROMETRIC |
| | RELIEF.THIS COMMENT HAS NOT BEEN |
| | PROPERLY ADDRESSED. THE REVISION MADE IS |
| | NOTED BUT THE NOTE SPECIFIES A MINIMUM |
| | PRESSURE DIFFERENCE OF 0.35"WG WHILE |
| | FBC 1005.6.9.9 REQUIRES A PRESSURE |
| | DIFFERENCE OF 0.05"WG MINIMUM AND |
| | 0.35"WG MAXIMUM.AMEND THE NOTE TO |
| | DEMONSTRATE COMPLIANCE. |
| | |
| | 54) TO EXPEDITE REVIEW OF A RESUBMITTAL |
| | WHICH REQUIRES NEW PLANS IN ORDER TO |
| | ADDRESS THE ABOVE COMMENTS, THE OLD |
| | SHEETS SHALL BE REMOVED AND THE NEW |
| | SHEETS INSERTED.ONE COPY OF EACH OLD |
| | SHEET SHOULD BE STAPLED/CLIPPED TO THE |
| | REMAINING OLD SHEETS FOR COMPARISON OF |
| | REVISIONS WHEN REVIEWING THE RESUBMITTED |
| | PLANS. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |
| | THE CODE REFERENCES GIVE ADDITIONAL INFO |
| | TELEPHONE: (561) 805 6716ROBERT BROWN |