| Date |
Text |
| 2004-02-10 00:00:00 | 1) PLEASE EXPLAIN HOW STAIRS ON THE |
| | LOADING DOCK CAN ACCOMODATE THE |
| | OCCUPANT LOAD FROM STAIR # 1. ALSO |
| | HOW WILL EXIT DISCHARGE BE MAINTAINED |
| | FROM THE EXIT DOOR OF STAIR # 1 THROUGH |
| | THE LOADING DOCK. |
| | |
| | 2) PLEASE EXPLAIN COMMENT PERMIT |
| | RESPONSE # 9. PLEASE CLARIFY. |
| | |
| | 3) FIRE ALARM NOTE ON PAGE FA1.03 IS |
| | INCORRECT. THE FIRE ALARM SYSTEM |
| | SHALL BE LISTED FOR CENTRAL STATION |
| | SERVICE. PLEASE REVISE. |
| | |
| | 4) ITEMS # 15 AND # 16 SHALL BE |
| | INDICATED ON THE PLANS. PLEASE REVISE. |
| | |
| | 5) NOTE # 18 PERMIT COMMENT RESPONSE |
| | NEEDS FURTHER CLARIFICATION. ANY |
| | ELECTRONIC LOCKS ON EXIT DOORS SHALL |
| | COMPLY WITH ACCESS CONTROL OR |
| | DELAYED EGRESS. PLEASE REVIEW |
| | APPLICABLE CODE SECTIONS AND ANNOTE |
| | PLANS. |
| | |
| | 6) HANDRAILS SHALL BE PROVIDED ON ALL |
| | NEW STAIRS. ALSO HANDRAILS ARE REQUIRED |
| | WITHIN 30" OF ALL REQUIRED WIDTHS USED |
| | FOR EXITING. |
| | |
| | 7) EXIT SIGN MISSING AT EXTERIOR DOOR |
| | OF STAIR # 3. |
| | |
| | 8) ONLY ONE FIRE HYDRANT SHOWN ON C-5. |
| | PLEASE CLARIFY. |
| | |
| | 9) NOTE # 29, NO PERMIT RESPONSE |
| | PROVIDED. |
| | |
| | MIKE CARSILLO, ASSISTANT FIRE MARSHAL |
| | 835-2910 |