Text |
| 2004-04-18 00:00:00 | ************** UNSAT **************** |
| | |
| | 1)NOTE: PLEASE SEE NOTE FROM LAST REVIEW |
| | PERTAINING TO INFORMATION REQ'D ON TITLE |
| | BLOCK FOR ENGINEER AND ENGINEERING FIRM. |
| | PLEASE SEE FAC 61G15-23.002,NAME OF |
| | ENGINEER, CERTIFICATE OF AUTHORIZATION |
| | IS REQ'D. PLEASE SEE FS 471.023 |
| | |
| | 2)NOTE: IT IS NOTED ON RISER FOR A |
| | MANUAL MEANS OF DISC FOR ATS/FIRE PUMP |
| | CONTROLLER BEFORE OPENING OF UNIT, |
| | HOWEVER SPECS SUBMITTED SHOW ONLY A |
| | POWER OPERATED MEANS OF DISC. |
| | PLEASE SEE 230.76/ 230.79/110.27 |
| | OPENING OF EQUIPMENT IS NOT PERMITTED |
| | BY FIRE DEPT PERSONNEL. |
| | PLEASE CLARIFY SIGNAGE NOTES AS REQ'D |
| | PER 230.2 REQUESTED ON PREVIOUS REVIEW. |
| | |
| | |
| | 3)NOTE: PLEASE SEE LOAD CALCULATIONS |
| | METER CENTERS SHOWN ON E3.01, THESE |
| | DO NOT SEEM TO CORRELATE WITH LOADS ON |
| | E4.01 DPS AND DPN. |
| | DEMAND KVA DEFERS FROM EACH SHEET. |
| | NEW COMMENT. |
| | |
| | 4)NOTE: PLEASE SEE CIRCUITS SHOWN FOR |
| | DINING RMM RECEPTS, 14,OR15?. PLEASE |
| | SEE 210.52B1 DINING RM CIRCUIT REQ'D |
| | TO BE 20A/ #12. |
| | NEW COMMENT. |
| | |
| | |
| | 5)NOTE: ONLY A NOTE, REDLINED RECEPT |
| | W/IN 6' OF DOOR UNIT"C1" E2.05 |
| | |
| | 6)NOTE: PLEASE SEE NOTE #10 FROM PREVI- |
| | -OUS REVIEW. NOTES NEED TO BE ADDED FOR |
| | HARDWARE AND DOORS PER 110.26 |
| | RESPONSE MENTIONS DOORS TO BE LOACKED |
| | AND ACCESSIBLE TO QUALIFIED PERSONNEL. |
| | PLEASE SEE THIS IS ONLY ONE OF THE |
| | REQ'MENTS. 110.26CNEEDS TO BE NOTED. |
| | |
| | PLEASE SEE FS 553.80(2)(B), A 4X FEE |
| | FOR PLAN REVIEW HAS BEEN ADDED TO TO |
| | ANY OF THE SAME COMMENTS FOR THREE OR |
| | MORE REVIEWS. PLEASE SEE BLDG REVIEW |
| | COMMETS. THIS FEE IS REQ'D TO BE PAID |
| | BEFORE RESUBMITTAL OF PLANS. PLEASE |
| | ALSO NOTE AN ADDITIONAL 10% RESUB FEE |
| | WILL ALSO BE DUE. |
| | THE AMOUNTS ARE AS FOLLOWS. |
| | $133,200.00 4X FEE FOR PLAN REVIEW FS553 |
| | $22,050.00 FOR 10% RE-SUB FEE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |