| Date |
Text |
| 2003-11-18 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FHA-98 DESIGN MANUAL |
| | FLORIDA STATUTES |
| | FLORIDA ADMINISTRATIVE CODE |
| | CITY WPB CODE |
| | |
| | A) MANY COMMENTS FROM THE FIRST REVIEW |
| | WERE NOT ADDRESSED AND NO COMMENT RES- |
| | PONSE NOTED. COMMENT NUMBERS FROM FIRST |
| | REVIEW WILL BE SHOWN FOR CLAIRITY. |
| | 1) SHTS A.11 & A.12, ALL PUBLIC & COMMON |
| | USE TOILET ROOMS SHALL COMPLY WITH SEC. |
| | 11-4.22 AND ALL SUBSECTIONS. (CLEAR |
| | FLOOR SPACE, HEIGHTS, GRAB BARS, ECT.). |
| | 2) PLEASE SUBMIT CALCULATIONS FOR MINI- |
| | MUM FIXTURE FACILITIES PER TABLE 403.1 |
| | FOR THE BUSINESS/COMMON AREAS GROUND |
| | FLOOR LEVEL, INCLUDE MGR, ASST. MGR, |
| | CONFERENCE ROOMS, HEALTH CLUB, FIRE |
| | CONTROL, SEC. DESK, VALET, MAIL ROOM, |
| | MAIN LOBBY, CARD ROOM, FITNESS CENTER, |
| | BAR, PANTRY, ECT. |
| | 3) SUBMIT CALCULATIONS FOR PRIMARY AND |
| | SECONDARY ROOF DRAINS. SHOW 1/2 AREA OF |
| | ALL VERTICAL WALLS INCLUDING PARAPETS |
| | AND AREA OF ROOFS THAT DRAIN FROM ABOVE |
| | ON TO ROOF ADDED TO SQUARE FOOTAGE OF |
| | ROOF. SHOW HOW EACH AREA WILL BE AFFECT- |
| | ED BY VERTICAL WALLS AND ROOF DRAINING |
| | FROM ABOVE, INDICATE HOW THE INTERNAL |
| | ROOF AEAS, (WITHOUT SCUPPERS), ADD TO |
| | SCUPPER SIZE OF ADJACENT AREAS. SECTIONS |
| | 1106 & 1107 AND ALL SUBSECTIONS. |
| | 4) SHT A.09, INDICATE LOCATION OF SECON- |
| | DARY DRAINS FOR THE DECK AREA AROUND THE |
| | POOL, AND DECK AREAS BELOW THE POOL DECK |
| | AREA. |
| | 6) SHTS A.51 THRU A.66, LAV ELEVATIONS |
| | MAXIMUM 34" TO TOP. FHA DESIGN MANUAL |
| | PAGE 7.52. |
| | 7) SHTS A.51 THRU A.66, SPECIFICATION |
| | "A" OR "B" SHALL BE NOTED ON PLANS FOR |
| | BATHROOMS PER FHA DESIGN MANUAL PAGE |
| | 7.35. |
| | 8) SHTS A.51 THRU A.66, UNIT PLAN NOTES: |
| | #7, SUBMIT CALCULATIONS FOR 20GA METAL |
| | BACKING. SHOW COMPLIANCE WITH SECTIONS |
| | AA-4.26.3, 11-4.26.3(1), 11-4.26.3(2), |
| | 11-4.26.3(3), & 11-4.26.3(4). |
| | 9) SHTS A.51 THRU A.66 SHOW OPENING SIZE |
| | FOR ALL WATER CLOSETS. MINIMUM SIZE 33". |
| | (18" OFF WALL WHERE LOCATED NEXT TO ONE, |
| | AND MINIMUM OF 18" OFF FIXTURE). |
| | 10) SHT P1.01 SHOW PIPE SIZES AND CLEAN- |
| | OUT LOCATIONS. TABLE 710.1(1) & SECTIONS |
| | 708.3, 708.3.1, 708.3.3, 708.3.5. |
| | 23) SEPARATE GAS PERMIT REQUIRED. THE |
| | FOLLOWING INFORMATION IS REQUIRED FOR A |
| | PERMIT. |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2001 |
| | FUEL GAS CODE. - NOT ALL SECTIONS INDIC- |
| | ATE THE LENGTHS. |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. |
| | C. TYPE OF GAS, (LP OR NATURAL) |
| | E. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2001 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES (A)(3). - RECHECK |
| | DISTANCE. |
| | F. SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR (IF APPLICABLE) PER FBC-2001 FUEL |
| | GAS CODE SECTION 304. |
| | G. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2001 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | I. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2001 FUEL GAS CODE SEC 402.2 |
| | J. CLEARLY SHOW THE LOCATION AND CAP- |
| | ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| | OR ASME), THE DISTANCE OF THE TANK FROM |
| | THE BUILDING AND ADJACENT PROPERTY LINES |
| | THE DISTANCE OF THE TANK FROM ALL SOUR- |
| | CES OF IGNITION, OTHER CONTAINERS, BUILD |
| | INGS, AND THE LOCATION OF ANY BUILDING |
| | OPENINGS BELOW THE RELIEF VALVE OF THE |
| | TANK PER NFPA 58, TABLE 3-2.2.2. |
| | K. CLEARLY INDICATE ON THE PLAN IF THE |
| | LP TANK IS ABOVE OR BELOW GROUND, AND |
| | SHOW REQUIRED PROTECTION OF THE TANK AND |
| | APPURTENANCES PER NFPA 58. IF THE TANK |
| | IS BELOW GROUND THE CONTAINER SHALL BE |
| | SECURILY ANCHORED PER NFPA 58 SECTION |
| | 3-2.2.7(H). |
| | *********WHEN RESUBMITTING PLANS******** |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| | THE PLANS WHEN RESUBMITTING PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN |
| | BE FOUND, WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | **************************************** |
| | NEW COMMENTS |
| | 1B) SHT A.12 WALLS IN MEN'S & WOMEN'S |
| | TOILET ROOMS APPEAR TO BE IN TURNING |
| | CIRCLE AND IN HDCP STALLS. PLEASE REMOVE |
| | 2B) SUBMIT A DETAIL FOR ACCESSIBLE |
| | TOILET ROOMS PER 11-4.16, 11-4.19, AND |
| | 11-4.22 AND ALL SUBSECTIONS. |
| | 3B) SHT A.11 BAR SINK SHALL COMPLY WITH |
| | 11-4.24 AND ALL SUBSECTIONS. PROVIDE A |
| | DETAIL. |
| | 4B) SHT A.45 OVERFLOW SCUPPER DETAIL. |
| | SCUPPER SHALL BE PLACED IN WALLS OR |
| | PARAPETS WITH THE INLET FLOW LINE NOT |
| | LESS THAN 2 INCHES ABOVE THE ROOF SUR- |
| | FACE, EXCLUDING SUMPS, OR MORE THAN 4 |
| | INCHES ABOVE THE ROOF SURFACE AND SHALL |
| | BE LOCATED AS CLOSE AS PRACTICAL TO REQ- |
| | UIRED VERTICAL LEADERS. |
| | 5B) SHTS A.51 THRU A.66 SHOW CLEAR FLOOR |
| | SPACE FOR ALL ACCESSIBLE FIXTURES PER |
| | FHA DESIGN MANUAL PAGE 7.43 |
| | 6B) SHTS A.51 THRU A.66 UNIT PLAN NOTES: |
| | #6 STATE 1996 FHA - UPDATE TO READ AMEND |
| | ED 1998 FHA. |
| | 7B) SHT P1.01 KEY NOTES: #8 & STORM |
| | DRAIN, 3" FIRE STAND PIPE DRAIN NOT APP- |
| | ROVED TO STORM. DRAIN SHALL CONNECT TO |
| | SANITARY VIA INDIRECT WASTE. CITY CODE |
| | SECTION 90-233(A). |
| | 8B) SHTS P1.01 & P1.02 MORE INFORMATION |
| | REQUIRED FOR PAD RISER. SEE #'S 14 & 37 |
| | KEY NOTES. |
| | 9B) SHT P1.02 FLOOR DRAINS FOR FIRE AND |
| | DOMESTIC PUMP ROOMS SHALL CONNECT TO |
| | SANITARY, NOT STORM. CITY CODE 90-233(A) |
| | 10B) 61G15-23.002(1) SIGNATURE REQUIRED |
| | ON SEAL. PER FBPE INITALS ARE NOT TO BE |
| | ACCEPTED. THE SIGNATURE THAT WAS SIGNED |
| | ON THE ENGINEERS LICENSE SHALL BE RE- |
| | QUIRED ON EACH SHEET. |
| | 11B) SHT P1.04 RISER DIAGRAM DOES NOT |
| | REFLECT THE FLOOR PLAN FOR UNIT 1. |
| | SECTION 104.2.1 |
| | 12B) SUBMIT RISER DIAGRAMS FOR RELIEF |
| | VALVE DISCHARGE LINE (P&T) FOR W/HEATERS |
| | THE DISCHARGE LINE FOR RELIEF VALVE |
| | SHALL NOT HAVE ANY TRAPPED SECTIONS AND |
| | SHALL HAVE A VISIBLE AIR GAP OR AIR GAP |
| | FITTING IN THE SAME ROOM AS THE WATER |
| | HEATER. SEC 504.7.1 |
| | 13B) SHT P3.01 12" @ 3085 DFU'S AND 12" |
| | @ 3419 DFU'S NOT APPROVED PER TABLE |
| | 710.1(1). |
| | 14B) SHT P3.03 RISER S/19, 3" REQUIRED |
| | TO SHOWER. TABLE 909.3 |
| | 15B) BACKFLOW PROTECTION REQUIRED FOR |
| | TRASH CHUTE RING. SECTION 608.13 SUBMIT |
| | DETAIL. |
| | 16B) SHT P3.05 KEY NOTES: #22, CLAIRFY |
| | 15TH FLOOR. #17 NOT FOUND. (2) # 19'S |
| | 17B) SHT P3.05 SUBMIT CALCULATIONS FOR |
| | WATER PRESSURE AT BOTTOM OF DROPS FOR |
| | UNITS TO DETERMINE OF A PRESSURE REGULA- |
| | TOR IS REQUIRED. |
| | 18B) SHT P3.06 FILTER FOR ICE MACHINE |
| | SHALL COMPLY WITH NSF STANDARD FOR WATER |
| | FILTERS. SUBMIT MANUFACTURE SPECIFICAT- |
| | ION SHEETS. SECTION 303.4 |
| | 19B) SHT P3.06 WATER HAMMER ARRESTORS |
| | REQUIRED AND ICE MACHINE AND DISHWASHER. |
| | SECTION 604.9 |
| | 20B) SHT P3.09 STORM DRAIN COLLECTION |
| | ISOMETRIC, DOWNSTREAM OF RWL'S 24 & 25 |
| | SHOWS 6"(5280 SF). MINIMUM 8" PIPE REQD. |
| | 21B) SHT P3.09 STORM DRAIN COLLECTION |
| | ISO., DOWNSTREAM OF (A) SHOWS 6" (2840 |
| | SF) THEN SHOWS 4" PLEASE REVISE. 704.2. |
| | 22B) SHT P3.09 STORM DRAIN COLLECTION |
| | ISO., PLANTER DRAINS SHOW 40SF PLUS 200 |
| | SF, BUT ONLY ADDS UP TO 80SF. AND AFTER |
| | 6" DD (3300SF) PLUS (240SF) SHOWS (3380 |
| | SF) BUT SHOULD READ (3540SF) PLEASE RE- |
| | VISE. - INDICATE SF FOR FORCE MAIN FROM |
| | BELOW. - ALSO DOWNSTREAM OF PD (1040SF) |
| | SHOWS (900 SF) REVISE. |
| | 23B) PROVIDE INFORMATION FOR FSP DRAIN. |
| | WHAT TYPE OF DRAIN IS THIS AND WHAT DOES |
| | IT DRAIN? |
| | 24B) SHT P3.10 PROVIDE MANUF. SPECC. |
| | SHEETS ON STORM DRAIN LIFT STATION. |
| | 25B) SHT P3.10 FIRE STAND PIPE DRAIN |
| | SHALL NOT DRAIN TO STORM. CONNECT TO |
| | SANITARY SYSTTEM. |
| | 26B) SHT P3.11 PROVIDE CUT PIECE MEAS- |
| | URMENTS FROM METER TO FIRST GAS RISER & |
| | MEASURMENTS FOR ALL CUT PIECES IN BOILER |
| | ROOM. |
| | 27B) SHT P3.11 GAS ISOMETRIC, INDICATE |
| | WHY GAS LINE TO POOL EQUIPMENT ROOM IS |
| | SLEEVED. PIPING SHALL NOT BE INSTALLED |
| | IN SOLID FLOOR SLABS. SECTION 404.6 |
| | 28B) SHT P3.11 NFPA-54 HAS NOT BEEN |
| | ADOPTED. SIZE PIPE PER FBC-2001 FUEL GAS |
| | DELETE REFERENCE. |
| | 29B) SHT P3.12 CONDENSATE COLLECTION ISO |
| | MINIMUM 2" PIPE UNDERGROUND. SECTION |
| | 710.3 |
| | 30B) SHT P3.12 COND. COLLECTION ISO., A |
| | RELIEF VENT IS REQUIRED AS CONDENSATE |
| | EXITS THE BLDG. |
| | 31B) SHTS P1.03, THRUP1.09, & P2.01 |
| | UNIT "A", RISER S/70 RISER NOT FOUND AND |
| | RISER S/18 DOES NOT REFLECT THE FLOOR |
| | PLAN. SHT P3.04 |
| | 32B) SHT P3.03 RISER S/19 TABLE 909.3 |
| | 3" REQUIRED TO SHOWER. |
| | 33B) SHTS P1.03 THRU P1.09 & P2.01 UNIT |
| | "A" MOD, RISER S/71 NOT FOUND AND RISER |
| | S/53 DOES NOT REFLECT THE FLOOR PLAN. |
| | SHT P3.04. |
| | 34B) SHT P3.04 RISER S/59 DOES NOT RE- |
| | FLECT THE FLOOR PLAN. |
| | 35B) SHT P3.04 RISER S/62 DOES NOT RE- |
| | FLECT THE FLOOR PLAN. |
| | 36B) SUBMIT MANUF. SPEC. SHEET FOR SIM- |
| | PLEX AND TRIPLES PUMP SYSTEMS. |
| | 37B) SEE ATTACHED SHEET CONCERNING |
| | FS 533.80(2)(B) DESIGN PROFESSIONAL DOC- |
| | UMENTS. |
| | *********WHEN RESUBMITTING PLANS******** |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| | THE PLANS WHEN RESUBMITTING PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN |
| | BE FOUND, WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |