| Date |
Text |
| 2003-11-19 00:00:00 | DENIED: |
| | PLEASE PROVIDE TRANSMITTAL LETTER WITH |
| | RESPONSES TO COMMENTS TO HELP EXPEDITE |
| | PLANS IN A MORE TIMELY MANNER. |
| | |
| | 1.PLAN SHEET A.45B DETAIL G, DRYER |
| | VENT TO BE NON-SCREENED WITH A BACKDRAFT |
| | DAMPER AND SHALL NOT PASS THRU PLENUMS |
| | PER 2001 FBC(M) 504.4. |
| | |
| | 2.PLAN SHEET M1.03 CLARIFY MAKE-UP AIR |
| | NEXT TO STAIRWELL PRESSURE RELIEF |
| | (EXHAUST). |
| | |
| | 3.M1.03-INDICATES FLAMEBAR DUCT IN |
| | STAIRWELL. PER 2001 FBC 1006.1.3.1, NO |
| | DUCT PENETRATIONS THROUGH A STAIRWELL |
| | EXCEPT FOR STAIRWELL PRESSURIZATION. |
| | PLEASE PROVIDE SUBMITTAL FOR THE |
| | FLAMEBAR DUCT. |
| | |
| | 4.M1.03-PROVIDE MANUFACTURER SUBMITTAL |
| | DATA ON THE GENERATOR WILL THERE BE A |
| | FILL TANK OR STORAGE? |
| | |
| | 5.SUPPLY DUCT FROM HP-G-1 APPEARS TO |
| | PENETRATE A RATED WALL AT THE ELEVATOR |
| | LOBBY AREA.FIRE DAMPERS ARE NOT |
| | REQUIRED AS LONG AS ALL THE CONDITIONS |
| | OF 607.1.3. |
| | |
| | 6.FLOORS 2 THRU 8 SUPPLY DUCT FROM |
| | HP-C-1 REQUIRE A FIRE DAMPER AT THE |
| | PENETRATION THRU THE WALL TO THE |
| | CORRIDOR. |
| | |
| | 7.M1.03 THRU M1.09 INDICATE DOORS WITH |
| | UNDERCUTS AND LOUVERS ARE THESE FIRE |
| | RATED CORRIDORS?PLEASE CLARIFY. |
| | |
| | 8.M1.03 FIRE/SMOKE DAMPERS MISSING |
| | FROM HP-G-5 WHERE DUCT PASSES THRU RATED |
| | WALLS.PLEASE CLARIFY. |
| | |
| | 9.M2.01 & OTHERS INDICATE EXHAUST ON |
| | TERMINATING ONTO THE TERRANCE PLEASE |
| | NOTE PER 2001 FBC(M) 401.5.2, EXHAUST |
| | OPENINGS SHALL BE LOCATED SO AS NOT |
| | CREATE A NUISANCE. EXHAUST AIR SHALL NOT |
| | DIRECTED ONTO WALKWAYS. |
| | |
| | 10. M2.01 NOTE ON PLAN INDICATES SPECFIC |
| | DRYERS TO BE INSTALLED FOR INCREASED |
| | VENTING CAPABILITY.PLEASE PROVIDE |
| | MANUFACTURER SPECS FOR DRYER.DRYERS |
| | TO BE INSTALLED FOR FINAL INSPECTION. |
| | |
| | 11. M.401 SMOKE CONTROL - PRESSURIZATION |
| | OF CORRIDOR PLEASE CLARIFY HOW THIS |
| | COMPLYS WITH 2001 FBC 412.5.WHERE WILL |
| | THE SMOKE ON THE FLOOR OF INCIDENT BE |
| | MIDIGATED TO? |
| | |
| | 12. AUXILIARY DRAIN PANS REQUIRED PER |
| | 2001 FBC(M) 307.2.3. |
| | |
| | 13. PROVIDE OUTSIDE AIR CALCULATIONS FOR |
| | ALL AREAS COMMON AND RESIDENTIAL PER |
| | 2001 FBC(M) 403.3. |
| | |
| | 14. PROVIDE CALCULATIONS FOR COMBUSTION |
| | AIR IN THE BOILER ROOM.PROVIDE MIMINUM |
| | AIR REQUIREMENTS FOR ALL THE MECHANICAL |
| | ROOMS.INDICATE CALCULATIONS ON PLAN. |
| | |
| | 15. PLEASE NOTE EXHAUST CONTAINING |
| | NOXIOUS FUMES, DUST PARTICALS OR SMOKE |
| | SHALL BE LOCATED A MINIMUM OF 10 FT |
| | FROM ANY FRESH AIR INTAKE (INCLUDING |
| | DOORS AND WINDOWS). |
| | |
| | 16. PLEASE INDICATE IF ANY OF THE |
| | APPLIANCES ARE GAS. |
| | |
| | 17. PLEASE NOTE AS PER FS 471.025 AND |
| | FAC 61G15-23.003, ALL PLANS SHALL BE |
| | SIGNED (NOT INITIALED), SEALED AND DATED |
| | BY THE ENGINEER OF RECORD.PLEASE |
| | REVISE PLANS TO COMPLY. |
| | |