| Date |
Text |
| 2003-10-30 00:00:00 | 1) STAIR # 4 DOOR ON PAGE A.02 SWINGS |
| | IN THE WRONG DIRECTION. DOOR SWINGS |
| | OUT, SHOULD SWING IN. B-2 LEVEL. |
| | |
| | 2) SAME CONDITION, SAME LOCATION OCCURS |
| | ON PAGE A.03. B-1 LEVEL. |
| | |
| | 3) PLEASE EXPLAIN EXITING RATIONALE |
| | FROM THE BUILDING. PLEASE INDICATE |
| | WHICH STAIRS LEAD DIRECTLY TO THE |
| | EXTERIOR AT GROUND LEVEL. |
| | |
| | 4) COURTYARD AREA DISPLAYS STAIRS ABSENT |
| | OF HANDRAILS. |
| | |
| | 5) PLEASE EXPLAIN HOW EXITING OCCURS |
| | NEAR THE BIKE STORAGE AREA. IT APPEARS |
| | THRU THE LOADING DOCK. PLEASE EXPLAIN |
| | RATIONALE. |
| | |
| | 6) STAIR # 1 APPEARS TO DISCHARGE ONTO |
| | THE LOADING DOCK. PLEASE EXPLAIN. |
| | |
| | 7) KNOX-BOX NOT REQUIRED IN FIRE |
| | COMMAND ROOM. KNOX-BOXES ARE REQUIRED |
| | TO GAIN ACCESS FROM THE EXTERIOR OF |
| | THE BUILDING. THEY ARE NOTED ON THE |
| | DRAWINGS. |
| | |
| | 8) ALL PREVIOUSLY PLAN REVIEW COMMENTS |
| | NOTED ON JUNE 6, 2003 HAVE NOT BEEN |
| | ADEQUATELY ADDRESSED. |
| | |
| | 9) PLEASE EXPLAIN "SMOKE DETECTOR NOTE |
| | ON FA1.10 CONNECT DELUGE SYSTEM TO |
| | FIRE ALARM PANEL AS REQUIRED". |
| | |
| | 10) FIRE ALARM EQUIPMENT NOTED IN |
| | STAIR # 2. PLEASE REVIEW CODE SECTIONS |
| | FOR ITEMS ALLOWED IN STAIRWELL. |
| | |
| | 11) ALL FIRE ALARM SYSTEMS THAT |
| | SUPERVISE AUTOMATIC FIRE SPRINKLER |
| | SYSTEMS AS OF AUGUST 1, 2003, MUST BE |
| | UL LISTED FOR CENTRAL STATION SERVICE. |
| | |
| | 12) FPS.02 DISPLAYS THREE FIRE |
| | DEPARTMENT CONNECTIONS. ONLY TWO ARE |
| | NEEDED. |
| | |
| | 13) NOTE # 29 ON FP3.01 IS INCORRECT. |
| | STANDPIPES ERECTED DURING CONSTRUCTION |
| | ARE REQUIRED WHEN CONSTRUCTION REACHES |
| | 30 FEET NOT 50 FEET. |
| | |
| | 14) ALL SPRINKLERS SHALL BE QUICK |
| | RESPONSE TYPE. |
| | |
| | 15) TACTILE SIGNAGE REQUIRED AT ALL |
| | STAIRWELLS. |
| | |
| | 16) HOW IS THE 4" PIPING FOR THE |
| | STANDPIPE SYSTEM THAT RUNS BELOW |
| | THE POOL DECK GOING TO BE INSPECTED |
| | OR MAINTAINED IN THE FUTURE. |
| | |
| | 17) SMOKE CONTROL NOTES SHALL MENTION |
| | ANTICIPATED STACK EFFECT. |
| | |
| | 18) PLEASE EXPLAIN MAGNETIC LOCKS TIED |
| | TO FIRE ALARM SYSTEM. LOCKING |
| | DEVICES ON EXIT DOORS TO COMPLY WITH |
| | ACCESS CONTROLLED EGRESS WITH ALL |
| | CODE PARAMETERS BEING MET. |
| | |
| | 19) NO REVISIONS COULD BE LOCATED |
| | ON THE DRAWINGS. |
| | |
| | 20) PLEASE PROVIDE PRODUCT APPROVALS |
| | FOR INSULATION PLANNED FOR AROUND |
| | TRASH CHUTE. |
| | |
| | 21) PLEASE PROVIDE STRENGTH REQUIREMENTS |
| | FOR HANDRAILS. |
| | |
| | 22) ALL CONCRETE STAIRS ON RECREATION |
| | DECK SHALL BE EQUIPPED WITH HANDRAILS |
| | ON BOTH SIDES. |
| | |
| | 23) HANDRAILS ARE REQUIRED FOR STAIRS |
| | ON UPPER PLAZA. |
| | |
| | 24) PROVIDE CONSTRUCTION DATA. |
| | |
| | 25) BUILDING ADDRESS REQUIRED. |
| | |
| | MIKE CARSILLO, ASSISTANT FIRE MARSHAL |
| | 835-2910 |