| 2003-11-04 00:00:00 | ******************** UNSAT ************* |
| | |
| | PLEASE SEE NOTES FROM OTHER REVIEWERS |
| | THAT MAY HAVE AN AFFECT ON ELECTRICAL |
| | PLANS. |
| | |
| | 1)NOTE: PLEASE SEE 700.16 FOR LIGHTING |
| | IN ELECTRICAL RMS AND THE LIKE. |
| | |
| | 2)NOTE: PLEASE SEE NOTE FOR LIGHTNING |
| | PROTECTIONS SYSTEM REFERENCES NFPA 78, |
| | SHOULD READ 780. (MISPRINT). |
| | |
| | 3)NOTE: PLEASE CLARIFY MEANS OF EGRESS |
| | LIGHING ON GRADE LEVEL ACCESS FROM |
| | GROUND FLR UNITS EXITING TO STREET. |
| | 210.70 AND LS 101 |
| | |
| | 4)NOTE: PLEASE SEE THAT POOL PERMIT WILL |
| | BE REQ'D TO BE UNDER SEPARATE PERMIT |
| | ANDWILL REQUIRE A WIRING DIAGRAM FOR |
| | POOL EQUIPMENT AT THAT TIME. |
| | |
| | 5)NOTE: PLEASE SEE PLANS FOR UNITS, |
| | STARTING AT E2.01. KEYNOTES MENTION FOR |
| | RECEPTS TO HAVE ARC FAULT PROETCTION, |
| | HOWEVER, PANEL SCHEDULES MENTION TO SEE |
| | NOTES AND THOSE NOTES MENTION LTS AND |
| | RECEPTS? PLEASE SEE 210.12. |
| | PLEASE SEE THE STATE ADOPTED THE 2002 |
| | NEC ON 7/1/03. |
| | |
| | 6)NOTE: PLEASE SEE THAT WHEN BATHROOMS |
| | ARE WIRED TO HAVE ALL LIGHTING AND GFI |
| | RECEPT ON ONE CIRCUIT AS PERMITTED UNDER |
| | 210.11C3, NO OTHER AREAS INCLUDING |
| | ADDTIONAL BATH(S) MAY BE FED. PLEASE |
| | ADJUST ALL CIRCUITING ON PLANS AND |
| | PANEL SCHEDULES. |
| | PLEASE ALSO SEE 210.52D FOR A COUPLE OF |
| | MISSING GFI RECEPTS. (B-5) |
| | |
| | 7)NOTE: PLEASE SEE 210.52 FOR RECEPT |
| | SPACING. PLEASE SEE 2' OF WALL SPACES |
| | IN MANY UNITS. ONE SET HAS MANY HIGH- |
| | -LIGHTED ON YELLOW. |
| | |
| | 8)NOTE: PLEASE PROVIDE INFORMATION FOR |
| | FIRE PUMP OCP ETC PER 695.4B |
| | DISC MEANS? SIGNAGE/NOTES ETC. 230.2, |
| | 230.72 ETC. |
| | PLEASE SEE THAT THIS INFORMATION IS |
| | REQ'D ON THESE PLANS. PLEASE ALSO NOTE |
| | IF ALL SUBMITTALS FOR GENERATOR SYSTEM |
| | IS NOT SUBMITTED WITH THIS PACKAGE THEN |
| | GENERATOR SYSTEM WILL BE REQ'D TO BE |
| | UNDER SEPARATE PERMITS AND ALL ADDTIONAL |
| | FEES WILL BE REQ'D AT THAT TIME ALSO. |
| | |
| | 9)NOTE: PLEASE PROVIDE INFORMATION FOR |
| | MSBR, SHOWN AS HAVING 3 SPACES? AS THIS |
| | EQUIPMENT IS A MLO UNIT. PLEASE CLARIFY |
| | |
| | 10)NOTE: PLEASE PROVIDE A NOTE ON ELEC- |
| | -TRICAL AND BLDG PLANS FOR REQUIREMENTS |
| | OF 110.26 AND TYPE OF HARDWARE REQ'D |
| | ON ELECTRICAL ROOM DOORS THAT MEET. |
| | 110.26 |
| | |
| | 11)NOTE: PLEASE SHOW ALL CONTINUOUS LOAD |
| | -S AT 125% PER 215.3,230.42 ETC. |
| | INCLUDING LARGEST MOTOR LOADS. |
| | |
| | 12)NOTE: PLEASE CLARIFY HOW BOTH PANEL |
| | "H" AND "HA" ARE SHOWN AS SEC 1O2. |
| | |
| | 13)NOTE: PLEASE CLARIFY METHOD OF |
| | WATER HEATER? |
| | |
| | 14)NOTE: PLEASE SEE FAC 61G15-23.002 AND |
| | PLEASE INCLUDE ALL INFORMATION SET FORTH |
| | AND REQUIRED PER THIS AND FS 471 |
| | THIS IS REQ'D FOR ALL TRADES WEATHER OR |
| | NOT COMMENTED ON. |
| | |
| | 15)NOTE: PLEASE SEE COPY OF FS 553.80(2) |
| | (B) ATTACHED. THIS IS REQ'D TO GO OUT |
| | ON ANY PROJECT OF REVIEW THAT HAS HAD |
| | ONE/OR ANY OF THE PREVIOUS COMMENTS THE |
| | SECOND TIME. THIS IS ONLY A NOTICE. |
| | |
| | PLEASE NOTE: A RESPONSE LETTER WILL |
| | USUALLY HELP THE PROCESS OF PLAN REVIEW |
| | AND BEING ABLE TO ISSUE PERMIT. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | INSERT NEW SHEETS INTO TWO COMPLETE SETS |
| | FOR REVIEW AND STAMPING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |