| Date |
Text |
| 2005-06-13 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | FBC-2001 CHAPTER 1 |
| | |
| | |
| | 1. SHT P1.01 REVISION 7 NOT FOUND. |
| | PLEASE CLOUD AND NUMBER EACH REVISION. |
| | SECTION 104.2.1. |
| | 2. SHT P1.02 REVISION 6 NOT FOUND. |
| | PLEASE CLOUD AND NUMBER EACH REVISION. |
| | SECTION 104.2.1. |
| | 3. SHT P1.03 FOLLOWING TO NOT MEET CODE: |
| | A. TUB NOT VENTED UNIT B1.1 BATH #2 |
| | B. INDICATE WHERE S/14 RISER CONNECTS |
| | TO THE BLDG. DRAIN. SECTION 104.2.1. |
| | C. UNIT STUDIO "S2" TOILET IS NOT |
| | VENTED. LAV SHOULD VENT THE BATHROOM |
| | FIXTURES AND KITCHEN SINK/WASH MACHINE |
| | SHALL DISCHARGE DOWNSTREAM OF THE WET |
| | VENT. SECTIONS 901.2.1 & 909.1. |
| | D. 2" PIPE FEEDING THE HOSE BIBB? |
| | PLEASE CLARIFY. SECTION 104.2.1. |
| | E. UNIT A2 UNABLE TO READ RISER |
| | DESIGNATION OVER A/C UNIT. SECTION |
| | 104.2.1. |
| | F. REVISIONS 2, 3, & 4 NOT FOUND. |
| | PLEASE CLOUD AND NUMBER EACH REVISION. |
| | SECTION 104.2.1. |
| | 4. SHT P1.04 REVISION #1 NOT FOUND. |
| | PLEASE CLOUD AND NUMBER ALL REVISIONS. |
| | SECTION 104.2.1. - SEE UNIT "B2" LAV |
| | CONNECTION TO BRANCH LINE NOT DIRECTING |
| | WASTE IN DIRECTIONS OF FLOW. SECTION |
| | 706.3. (COL. LINE W.K) |
| | 5. SHT P1.05 REVISION #1 NOT FOUND. |
| | PLEASE CLOUD AND NUMBER ALL REVISIONS. |
| | SECTION 104.2.1. - TWO NUMBER 46 RISERS |
| | BUT NO NUMBER 47. PLEASE CLARIFY. |
| | 6. SHT P1.06 REVISION #1 NOT FOUND. |
| | PLEASE CLOUD AND NUMBER ALL REVISIONS. |
| | SECTION 104.2.1. - SHEET INDICATES |
| | "TYPICAL FLOOR PLAN - PLUMBING" FOR |
| | WHICH FLOORS? SECTION 104.2.1. - TWO #46 |
| | SANT. RISERS AND NO #47 SANT. RISER. |
| | PLEASE CLARIFY. |
| | 7. SHT P1.07 REVISION #1 NOT FOUND. |
| | PLEASE CLOUD AND NUMBER ALL REVISIONS. |
| | SECTION 104.2.1. - TWO #46 RISERS AND NO |
| | #47 RISER FOUND. PLEASE CLARIFY. |
| | 8. SHT P1.08 REVISION #1 NOT FOUND. |
| | PLEASE CLOUD AND NUMBER ALL REVISIONS. |
| | SECTION 104.2.1. - SHOW ALL RISER |
| | DESIGNATION NUMBERS. SECTION 104.2.1. |
| | 9. SHT P1.09 REVISION #1 NOT FOUND. |
| | PLEASE CLOUD AND NUMBER ALL REVISIONS. |
| | SECTION 104.2.1. - TWO NUMBER 46 SANT. |
| | RISERS AND NO #47 RISER FOUND. PLEASE |
| | CLARIFY. |
| | 10. SHT P1.10 THE FOLLOWING SANT. RISERS |
| | SHOW UP ON THIS SHEET, BUT WERE NOT |
| | NOTED ON THE PREVIOUS SHEETS FROM THE |
| | GROUND FLOOR UP. S/16, S/33, S/51, & |
| | S/63 PLEASE CLARIFY.-INDICATE THE |
| | LOCATION OF VTR FOR SANT. RISER 74. - |
| | RISER S/63 DOES NOT REFLECT THE ROOF |
| | PLAN. THE FLOOR DRAIN IS NOT SHOWN ON |
| | RISER. PLEASE CORRELATE RISER WITH FLOOR |
| | PLAN. - FLOOR DRAIN BY S/64 NOT PIPED TO |
| | ANY SANT. RISER. PLEASE CLARIFY. SECTION |
| | 104.2.1. |
| | 11. SHT P3.01 SANT. RISER S/8 OFFSET |
| | VENT REQUIRED. SECTION 915 - VENT STACK |
| | SHALL CONNECT AT OR BELOW THE THE LOWEST |
| | HORIZONTAL BRANCH. SECTION 903.4. - |
| | STACK VENT SHALL RUN UNDIMINISHED IN |
| | SIZE AND AS DIRECTLY AS POSSIBLE FROM |
| | THE BUILDING DRAIN THROUGH TO THE OPEN |
| | AIR. SECTION 903.1. |
| | 12 SHT P3.01 SANT. RISER S/1 A VENT |
| | STACK IS REQUIRED PER SECTION 903.2 - |
| | VENT STACK CONNECTION APPEARS TO BE A |
| | HORIZONTAL DRY VENT. THIS IS NOT |
| | APPROVED PER SECTIONS 905.3 & 905.4. |
| | 13. SHT P3.01 SANT. RISER S/6-W/7, THE |
| | FITTING DOWNSTREAM OF STACKS PICKING UP |
| | THE W/M & TUB DOES NOT DIRECT THE WASTE |
| | IN THE DIRECTION OF FLOW AS REQUIRED IN |
| | SECTION 706.3. |
| | 14. SHT P3.01A SANT. RISER S/76 |
| | INDICATES FLOORS 3 THRU 7 TWICE, BUT NO |
| | FLOOR 8. PLEASE CLARIFY. SECTION |
| | 104.2.1. |
| | 15. SHT P301A SANT. RISER S/19 DOES NOT |
| | REFLECT THE FLOOR PLAN. SHOWER MISSING |
| | FROM RISER AND TUB SHOWN IN DIFFERENT |
| | LOCATION. PLEASE CORRELATE FLOOR PLAN & |
| | RISER DIAGRAM. SECTION 104.2.1. |
| | 16. SHT P3.01A FLOOR DRAIN NEAR SANT. |
| | RISER S/69 REQUIRES A RELIEF VENT FOR |
| | THE AIR ADMITTANCE VALVE. SECTION |
| | 917.3.2. |
| | 17. SHT P3.01C AIR ADMITTANCE VALVE NOT |
| | APPROVED FOR LIFT STATION. ONLY APPROVED |
| | FOR NEGATIVE PRESSURE. PLEASE SUBMIT |
| | MANUFACTURE SPECIFICATION AND |
| | INSTALLATION SHEETS FOR VALVE INDICATING |
| | APPROVAL FOR INSTALLATION FOR THIS TYPE |
| | OF APPLICATION.SECTION 303.2 |
| | 18. SHT P3.01C FLOOR SINK FOR INDIRECT |
| | WASTE FROM 3" FSP THE AIR ADMITTANCE |
| | VALVE REQUIRES A RELIEF VENT. SECTION |
| | 917.3.2. |
| | 19. SHT P3.01C BUILDING DRAIN LINES DO |
| | NOT REFLECT THE FLOOR PLAN DOWNSTREAM OF |
| | RISERS I, J, & K. ALSO THE PIPE SIZING |
| | FOR I, J, & K DO NOT REFLECT WHAT IS |
| | STATED IN KEY NOTES #10 WHICH IS 4". |
| | 20. SHT P3.01C INDICATE IF FLOOR DRAIN |
| | PIPING TO THE LIFT STATION. IT APPEARS |
| | TO BE ON THE FLOOR ABOVE. PLEASE |
| | CLARIFY. SECTION 104.2.1. - ALSO ALL |
| | THREE FLOOR DRAINS TO LIFT STATIONS ARE |
| | NOT VENTED. SECTION 901.2.1. |
| | 21. SHT P3.02 SANT. RISER S/30, TUB NOT |
| | VENTED AT THE BASE OF SANT. RISER. |
| | SECTION 901.2.1. |
| | 22. SHT P3.02 TOILET ROOM DOWNSTREAM OF |
| | RISERS 2/37-S/67 DOES NOT REFLECT THE |
| | FLOOR PLAN. LAV NOT SHOWN. CORRELATE |
| | FLOOR PLAN AND RISER. SECTION 104.2.1. - |
| | REVISIONS 2 & 3 NOT FOUND. PLEASE CLOUD |
| | AND NUMBER EACH REVISION. |
| | 23. SHT P3.02 SANT. RISER DIAGRAM, A |
| | VENT STACK IS REQUIRED, AND AN OFFSET |
| | VENT IS REQUIRED. SECTIONS 903.3 & 915. |
| | 24. SHT P3.02A BATHROOM DOWNSTREAM OF |
| | RISER S/53, THE LAV IS MISSING ON THE |
| | RISER DIAGRAM. THE LAV SHOULD VENT THE |
| | BATHROOM GROUP AND THE KITCHEN SHOULD |
| | CONNECT TO THE LINE WITH THE WASH |
| | MACHINE AND SHOULD NOT DRAIN THROUGHT |
| | THE HORIZONTAL WET VENT OF THE BATHROOM |
| | FIXTURES. SECTION 909.1. - THIS IS A NEW |
| | SHEET AND SHOWS 4 DIFFERENT REVISIONS. |
| | PLEASE CLARIFY. |
| | 25. SHT P3.03 SANT. RISER S/44 DOES NOT |
| | REFLECT THE FLOOR PLAN. WASH MACHINE IS |
| | MISSING. SECTION 104.2.1. - REVISIONS 2 |
| | & 3 NOT FOUND. PLEASE CLOUD AND NUMBER |
| | EACH REVISION. SECTION 104.2.1. |
| | 26. SHT P3.04 SANT. RISER S/58 DOES NOT |
| | REFLECT THE FLOOR PLAN, AND THE FIXTURES |
| | ARE MISLABLED AS LAVS. KITCHEN SINK |
| | MISSING 2ND FLOOR. SECTION 104.2.1. - |
| | REVISIONS 2 & 3 NOT FOUND. PLEASE CLOUD |
| | AND NUMBER EACH REVISION. SECTION |
| | 104.2.1. |
| | 27. SHT P3.09 REVISIONS 5 & 6 NOT FOUND. |
| | PLEASE CLOUD AND NUMBER EACH REVISIONS. |
| | SECTION 104.2.1. |
| | 28. SHT P3.11 NATURAL GAS ISOMETRIC: |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2001 |
| | FUEL GAS CODE. |
| | 28. SHT P3.12 REVISIONS 2 & 3 NOT FOUND. |
| | PLEASE CLOUD AND NUMBER ALL REVISIONS. |
| | SECTION 104.2.1. |
| | 29. SHT P4.01 REVISION #2 NOT FOUND. |
| | PLEASE CLOUD AND NUMBER EACH REVISIONS. |
| | SECTION 104.2.1. |
| | 30. THE FOLLOWING SHEETS WERE APPROVED |
| | AND ONE HAS BEEN ATTACHED TO FILE SET. |
| | P.1.11, P2.01. [2.02, P2.03, P2.04, |
| | P3.01B, P3.05, P3.06, & P4.02. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |