| Date |
Text |
| 2005-12-24 00:00:00 | ********** UNSAT ********** |
| | |
| | ** PLEASE SEE REVISONS FOR SOME UNITS |
| | WHICH WERE STAMPED ON 10/9/05 HAVE SINCE |
| | BEEN VOIDED. |
| | |
| | ** PLEASE SEE NOTE # 3 FROM SECOND |
| | REVIEW ON 10/9/05 HAS BEEN RECENDED. |
| | DOOR LOCATED TO SEPARATE BATHRM FROM |
| | BEDRM FOR UNITS3 |
| | |
| | ** PLEASE SEE THE FOLLOWING NOTES, |
| | PLEASE CORRELATE ALL UNITS AND SUBMIT |
| | REVISIONS FOR ALL UNITS. |
| | |
| | |
| | 1)NOTE: PLEASE SEE 210.52C1, C3, C4 FOR |
| | KITCHEN GFI RECEPT SPACING. PLEASE SEE |
| | SOME UNITS CONTAIN ADDED RECEPTS FOR |
| | AREA OF 12' OR MORE WALL SPACE AND |
| | PENINSULAR, HOWEVER SOME UNITS DO NOT |
| | SHOW THESE. |
| | PLEASE SEE ONLY ONE UNIT INDICATES A |
| | NOTE WITH RESPECT TO 12" OR MORE OF |
| | SPACE REQUIRING THE ADDITIONAL GFI. |
| | PLEASE SEE SOME UNITS SEEM TO CLEARLY |
| | INDICATE 12" OR MORE. |
| | |
| | 2)NOTE: PLEASE SEE WALL RECEPT MISSING |
| | IN B1C1 KIT WALL. |
| | 210.52 |
| | |
| | 3)NOTE: PLEASE SEE MANY UNITS HAVE BEEN |
| | REVISED TO LOCATE THE RECEPT FOR THE LV |
| | CONTROL PANEL ABOVE DOOR AND PLANS |
| | INCLUDE A NOTE FOR THIS ALSO, HOWEVER |
| | PLEASE SEE SOME UNITS WERE NOT CHANGED, |
| | PLEASE SEE MOST ALL UNITS STILL INDICATE |
| | A RECEPT IN PANEL AND SOME UNITS EVEN |
| | MOVED THE RECEPT ABOVE DOOR IN |
| | LAUNDRY/UTILITY RM? PLEASE KNOW, IF |
| | THESE PANELS ARE IN THE UTILITY ROOM |
| | THIS MOVING OF RECEPT ABOVE DOOR IS NOT |
| | REQUIRED. |
| | PLEASE ALSO CLARIFY WHY THERE IS A NOTE |
| | WHICH MENTIONS FOR GROUND FLR UNITS |
| | ONLY?? |
| | THIS WOULD BE REQUIRED IN ALL UNITS. |
| | |
| | 110.26.240.24 ETC |
| | |
| | PLEASE CALL TO GO OVER COMMENTS. |
| | WIRING TO UNITS SHOULD BE LIMITED UNTIL |
| | PLANS ARE CORRECTED AND CLEARED. |
| | |
| | A NOTICE WILL BE SENT TO THE CHEIF |
| | ELECTRICAL INSPECTOR AND ELECTRICAL |
| | INSPECTOR TO NOTIFY OF CORRECTIONS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |