| 2003-05-24 00:00:00 | DENIED:MECHANICAL PERMIT 03050109 |
| | PLEASE PROVIDE THE FOLLOWING INFORMATION |
| | FOR REVIEW: |
| | |
| | 1.PLAN SHEET M1.03 DUCTS PENETRATING |
| | WALLS WITH 1 HR RATING AT THE LOCATION |
| | OF THE MAIL RM, STORAGE RM & PUBLIC |
| | BATHROOMS.PLEASE INDICATE LOCATION OF |
| | THE FIRE DAMPERS. |
| | |
| | 2.PLAN SHEET 2.01, LINT TRAP WITH FAN |
| | BOOSTER INDICATED ON PLAN.PLAN SHEET |
| | M6.21 INDICATES A SUB-DUCT.PLEASE |
| | CLARIFY WHICH WILL BE USED. PLEASE NOTE, |
| | SHOULD THE SUBDUCT METHOD BE USED CLEAN- |
| | OUTS & SPRINKLER SYSTEM REQUIRED IN THE |
| | 2 HR SHAFT.SHOULD THE BOOSTER FAN |
| | METHOD BE USED PLEASE PROVIDE DETAIL |
| | OF "LINT TRAP".BOOSTER FAN MUST HAVE |
| | SOME TYPE OF NOTIFICATION IF IT FAILS. |
| | |
| | 4.PLEASE PROVIDE ELEVATION AT WHICH |
| | THE MUFFLER EXHAUST FROM THE GENERATOR |
| | WILL TERMINATE. |
| | |
| | 5.PLEASE PROVIDE OUTSIDE AIR CALCS |
| | FOR ALL AREAS COMMON AS WELL AS |
| | RESIDENTIAL.RESIDENTIAL CAN BE BY |
| | NATURAL MEANS AS PER 2001 FBC(M) 402.2 |
| | OR MECHANICAL TABLE 403.3. |
| | |
| | 6.A MINIMUM OF 4" CLEARANCE REQUIRED |
| | AROUND THE VERTICAL AHU AS PER 2001 FBC |
| | (M) 603.1.3. |
| | |
| | 7.AS PER 2001 FBC 411.4.2, THE |
| | MECHANICAL SYSTEM SHALL BE CAPABLE OF |
| | PROVIDING AT LEAST 6 AIR CHANGES PER |
| | HOUR FOR EACH LEVEL. |
| | |
| | 8.PLEASE PROVIDE CALCULATIONS FOR |
| | GARAGE, BOILER ROOM AND ALL EQUIPMENT |
| | AND MECHANICAL ROOMS. |
| | |
| | 9.PLEASE NOTE, MASTER BATHROOMS WHERE |
| | THE TOILET ROOM IS SEPARATE FROM THE |
| | BATHING AREA, A FAN WILL BE REQUIRED |
| | IN THE SHOWER AREA AS WELL AS THE TOILET |
| | AREA AS PER 2001 FBC(M) 402.3.1. |