2003-06-10 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION AND RESUBMIT FOR REVIEW.
  
 1} SHOW HOW THE NEW PANEL COMPLIES WITH
 250-32,225-31 NEC,AND 230-70 CWPB
 AMMENDMENTS.
  
 2} THE LOAD CALCULATIONS ARE INCOMPLETE.
 ON THE PLAN THERE ARE 2 AIR
 CONDITIONERS AND A WELDER THAT DO NOT
 APPEAR IN THE CALCULATION.PLEASE
 PROVIDE PANEL SCHEDULES FOR THE SERVICE
 EQUIPMENT.
  
 3} THE APPLICATION INDCATES THERE IS TO
 BE A HOBBY ROOM CHANGED INTO A BEDROOM.
 PLEASE CLARIFY THAT AREA ON THE PLAN.
 ALSO INDICATE COMPLIANCE WITH 210-12.
  
 4} PLEASE LIST THE REQ'D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.GFI PER 210-8.
  
 5} PLEASE NOTE THAT AN ELECTRICAL PERMIT
 IS REQUIRED FOR THIS PROJECT AND NONE
 WAS APPLIED FOR.AN ELECTRICAL PERMIT
 MUST BE OBTAINED PRIOR TO COMMENCING
 ANY ELECTRICAL WORK.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718