| 2003-06-10 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE PROVIDE THE FOLLOWING | | | INFORMATION AND RESUBMIT FOR REVIEW. | | | | | | 1} SHOW HOW THE NEW PANEL COMPLIES WITH | | | 250-32,225-31 NEC,AND 230-70 CWPB | | | AMMENDMENTS. | | | | | | 2} THE LOAD CALCULATIONS ARE INCOMPLETE. | | | ON THE PLAN THERE ARE 2 AIR | | | CONDITIONERS AND A WELDER THAT DO NOT | | | APPEAR IN THE CALCULATION.PLEASE | | | PROVIDE PANEL SCHEDULES FOR THE SERVICE | | | EQUIPMENT. | | | | | | 3} THE APPLICATION INDCATES THERE IS TO | | | BE A HOBBY ROOM CHANGED INTO A BEDROOM. | | | PLEASE CLARIFY THAT AREA ON THE PLAN. | | | ALSO INDICATE COMPLIANCE WITH 210-12. | | | | | | 4} PLEASE LIST THE REQ'D BATH(S) | | | CIRCUIT(S). PER 210-11-C-3 | | | MUST BE 20A AND #12AWG.GFI PER 210-8. | | | | | | 5} PLEASE NOTE THAT AN ELECTRICAL PERMIT | | | IS REQUIRED FOR THIS PROJECT AND NONE | | | WAS APPLIED FOR.AN ELECTRICAL PERMIT | | | MUST BE OBTAINED PRIOR TO COMMENCING | | | ANY ELECTRICAL WORK. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 |
|