| 2003-07-10 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: |
| | 1-PROVIDE COMPLETE/CORRECT INFORMATION |
| | FOR STORM SHUTTERS UNDER A SEPARATE |
| | PERMIT APPLICATION. |
| | 2-REVISE FOOTING AT REAR PORCH COLUMN, |
| | WHICH IS ENCROACHING INTO NEIGHBOR'S |
| | PROPERTY. |
| | 3-PROVIDE REVISED DETAIL FOR AIR HANDLER |
| | UNIT ATTACHED TO WALL. SHOW ALL REQ'D |
| | CLEARANCES. CLARIFY HOW IS THE UNIT |
| | REINFORCED TO BE WALL MOUNTED AND HOW |
| | IS VIBRATION TAKEN CARE OF. SECTION |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | 4-PROVIDE COMPLETE DETAIL/SPECS FOR |
| | INSTALLATION OF CEILING AT FRONT AND |
| | REAR PORCH. SPECIFY ALL MATERIALS, |
| | FASTENERS AND SPACING. SEE ASTM C926 |
| | AND ASTM C1063. |
| | 5-PROVIDE COMPLETE GABLE END DETAIL. |
| | SPECIFY EMBEDED ANCHOR AND SPACING. |
| | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| | 6-UPDATE TRUSS ANCHOR SCHEDULE AND ALL |
| | DETAILS THAT ARE AFFECTED BY SECTION |
| | 1609.4.3 FBC 2001, WHICH DOESN'T ALLOW |
| | THE STEEL STRESS TO BE INCREASED. |
| | **NOTE: SEE SIMPSON HIGH WIND-RESISTANT |
| | CONSTRUCTION CATALOGUE BECAUSE IS THE |
| | ONLY ONE THAT HAS BEEN REVISED TO |
| | REFLECT THIS CHANGE. |
| | 7-PROVIDE 2X STRUCTURAL BUCK DETAIL FOR |
| | ENTRY DOORS AND FIXED WINDOWS AS REQ'D |
| | ON THE PRODUCT APPROVALS. ALSO, SEE |
| | SECTION 1707.4.4.2 FBC 2001 FOR |
| | REQUIREMENTS ON BUCK INSTALLATION. |
| | 8-PROVIDE PRODUCT APPROVAL FOR: |
| | A)FIXED WINDOW WITH SIZES AS SHOWN ON |
| | PLANS ABOVE SLIDING GLASS DOOR IN THE |
| | GREAT ROOM AREA. |
| | B)GLASS BLOCK WITH LEGIBLE DRAWINGS. |
| | C)LEGIBLE DRAWINGS FOR ENTRY DOOR WITH |
| | RENEWAL STAMP BY DADE COUNTY. |
| | |
| | 9-SPECIFY SAFETY GLASS FOR GLASS BLOCK |
| | AT TUB AREA IF FACE THICKNESS IS LESS |
| | THAN 0.25". SEC. 2405.2 FBC 2001. |
| | |
| | NOTE: |
| | PLEASE CLOUD ALL REVISIONS TO EXPEDITE |
| | THE REVIEW PROCESS. |