| 2003-07-07 00:00:00 | BULDING REVIEW 2ND CHECKLIST: |
| | 1-PAY IMPACT FEES. BRING BACK STAMPED |
| | DRAWINGS AND RECEIPT. |
| | 2-WILL NEED TO RECORD A NOTICE OF |
| | COMMENCEMENT. |
| | 3-FOOTING PAD AT REAR PORCH COLUMN IS |
| | ENCROACHING INTO NEIGHBOR'S PROPERTY. |
| | REVISE AS REQUIRED. |
| | 4-AIR HANDLING UNIT HANGING DETAIL: |
| | A)DOESN'T PROVIDE THE CLEARANCES REQ'D |
| | BY SEC. 603.1.3 MECHANICAL FLORIDA |
| | BUILDING CODE 2001. |
| | B)IS UNIT BUILT TO BE HANGED FROM SIDE |
| | WALL OF UNIT?. IS IT REINFORCED?. |
| | PROVIDE MANUFACTURER'S INFORMATION |
| | THAT SHOWS THIS TYPE OF INSTALLATION. |
| | C)HOW IS VIBRATION TAKEN CARE OF. |
| | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| | |
| | 5-PROVIDE COMPLETE DETAILS/SPECS FOR |
| | INSTALLATION OF CEILING AT FRONT AND |
| | REAR PORCH. SPECIFY MATERIALS,FASTENER |
| | TYPE AND SPACING. SEE ASTM C-926 AND |
| | ASTM C-1063. |
| | 6-PROVIDE COMPLETE DETAIL FOR GABLE END. |
| | NEED TO SPECIFY TRUSS ANCHOR & SPACING |
| | SEE SEC. 2117 FBC 2001. |
| | 7-UPDATE TRUSS ANCHOR SCHEDULE AND ALL |
| | DETAILS THAT ARE AFFECTED BY SECTION |
| | 1609.4.3 FBC 2001. SEE SIMPSON HIGH |
| | WIND-RESISTANT CONSTRUCTION CATALOGUE |
| | WHICH HAS THE REVISED VALUES. |
| | 8-PROVIDE STRUCTURAL 2X BUCK DETAIL FOR |
| | ENTRY DOORS AND FIXED WINDOWS AS REQ'D |
| | ON THE PRODUCT APPROVALS. ALSO, SEE |
| | SEC. 1707.4.4.2 FBC 2001 FOR SPECIFIC |
| | BUCK INSTALLATION REQUIREMENTS. |
| | 9-PROVIDE PRODUCT APPROVAL FOR: |
| | A)FIXED WINDOW WITH SIZE AS SHOWN ABOVE |
| | SLIDING GLASS DOORS AND ABOVE WINDOW |
| | IN THE GREAT ROOM AREA. |
| | B)GLASS BLOCK WITH LEGIBLE DRAWINGS. |
| | C)LEGIBLE DRAWINGS FOR ENTRY DOOR WITH |
| | RENEWAL STAMP BY DADE COUNTY. |
| | |
| | 10-REVISE STORM SHUTTERS INFORMATION: |
| | A)REVISE MEAN ROOF HEIGHT AND DESIGN |
| | PRESSURES. |
| | B)REVISE MINIMUM AND MAX PANEL SPAN. |
| | SEE ENGINEERED DRAWINGS. |
| | C)INSTALLATION SCHEDULE: SPECIFY ANCHOR. |
| | D)DESIGN PRESSURES ARE MEASURED BY PSF |
| | NOT PSI. |
| | E)ADDITIONAL ENGINEERED DRAWINGS ARE NOT |
| | ALLOWED TO BE USED, UNLESS THEY ARE |
| | PART OF THE PRODUCT APPROVAL APPROVED |
| | BY SBCCI. |
| | F)CLEARLY MARK ON DRAWINGS SPECIFIC |
| | MOUNTING CONDITIONS, AND ANCHOR TYPE |
| | TO BE USED ACCORDING TO THE DESIGN |
| | PRESSURES, EDGE DISTANCE, PANEL SPAN, |
| | CONNECTION TYPE AND STRUCTURE TO BE |
| | ATTACHED TO. SEC. 104.2.1.2 CITY |
| | AMENDMENTS TO FBC 2001. |
| | |
| | 11-CONTRACTOR TO UPDATE INSURANCE. SEE |
| | CLERK TO UPDATE INFORMATION. |
| | 12-SPECIFY SAFETY GLASS FOR GLASS BLOCK |
| | AT TUB IF FACE THICKNESS IS LESS THAN |
| | 0.25". SEC. 2405.2 FBC 2001. |
| | 13-OWES $104.10 FOR UPDATED VALUATION |
| | AND RADON FEES. |
| | 14-PLEASE CLOUD ALL CHANGES IN THE |
| | DRAWINGS IN ORDER TO EXPEDITE THE |
| | REVIEW PROCESS. |
| | |
| | |
| | PLEASE CALL JULIO GOMEZ IF YOU HAVE ANY |
| | QUESTIONS OR NEED CLARIFICATION ON ANY |
| | OF THESE COMMENTS. |