| Plan Review Notes For Permit 03050068 |
| Permit Number |
03050068 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-05-17 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | | | | 1) SANITARY RISER DIAGRAM, OPTIONAL | | | LAUNDRY TUB SHALL NOT DRAIN INTO THE WET | | | VENT FOR THE BATHROOM FIXTURES. SECTION | | | 909.1 - L/TUB SHALL DRAIN DOWNSTREAM OF | | | BATHROOM FIXTURES. | | | 2) SHT A-6 PLUMBING NOTES #3, PIPES | | | 2-1/2" AND SMALLER SHALL BE PITCHED AT | | | 1/4" PER FOOT PER TABLE 704.1. PLEASE | | | CHANGE REFERENCE. | | | 3) SHT A-6 PLUMBING NOTES #7, AIR CHAMB- | | | ERS ARE NOT APPROVED. PDI-WH 201. | | | PLEASE DELETE REFERENCE. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 | | | (561) 805-6721 | | | FAX (561) 653-2692 |
|