| 2003-06-12 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1-PAY IMPACT FEES BRING BACK STAMPED |
| | DRAWINGS AND PAID RECEIPT. |
| | 2-NEED RECORDED NOTICE OF COMMENCEMENT. |
| | 3-FOOTING PAD AT REAR PORCH COLUMN IS |
| | ENCROACHING NEIGHBOR'S PROPERTY. |
| | REVISE AS REQUIRED. |
| | 4-AIR HANDLER UNIT: CLARIFY WHY IS THIS |
| | UNIT ATTACHED TO THE SIDE WALL AND NOT |
| | TO TOP OF TRUSSES AS TYPICALLY DONE. |
| | IS THIS UNIT BUILT/REINFORCED ON THE |
| | SIDE TO BE MOUNTED THIS WAY. AND, WHAT |
| | ABOUT VIBRATION OF THE UNIT. SECTION |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | 5-PROVIDE DETAILS AND SPECIFICATIONS FOR |
| | INSTALLATION OF CEILING AT FRONT AND |
| | REAR PORCH. SPECIFY MATERIALS AND |
| | FASTENER TYPE AND SPACING. SEE ASTM |
| | C-926 AND ASTM C-1063. |
| | 6-PROVIDE COMPLETE DETAIL FOR GABLE END. |
| | SEE SEC. 2117 FBC 2001 FOR SPECIAL |
| | WIND PROVISIONS FOR MASONRY. |
| | 7-UPDATE TRUSS ANCHOR SCHEDULE AND ALL |
| | DETAILS THAT ARE AFFECTED BY SECTION |
| | 1609.4.3 FBC 2001, WHICH DOESN'T ALLOW |
| | THE STREES INCREASE IN STEEL. SEE |
| | CURRENT CONNECTOR CATALOGUES FOR |
| | REVISED VALUES. |
| | 8-REVISE DETAIL 1/4-8 FOR FOOTING AREA |
| | AT GARAGE INTERIOR BEARING WALL. SHOW |
| | FOOTING WITH 6" RECESS AND DIMENSIONS |
| | SPECIFIED ON FOUNDATION PLAN.SEC. |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | 9-PROVIDE STRUCTURAL 2X BUCK DETAIL FOR |
| | ENTRY DOORS AND FIXED WINDOWS AS REQ'D |
| | ON THE PRODUCT APPROVALS. ALSO, SEE |
| | SEC. 1707.4.4.2 FBC 2001 FOR SPECIFIC |
| | BUCK INSTALLATION REQUIREMENTS. |
| | 10-PROVIDE PRODUCT APPROVAL FOR: |
| | A)FIXED WINDOW WITH SIZE AS SHOWN ABOVE |
| | SLIDING GLASS DOORS AND ABOVE WINDOW |
| | IN THE GREAT ROOM AREA. |
| | B)WINDOW & DOOR MULLIONS. SEE PLANS. |
| | C)GLASS BLOCK WITH LEGIBLE DRAWINGS. |
| | D)UPDATED ROOF TILE. SBCCI REPORT THAT |
| | WAS SUBMITTED WAS DELETED BY SBCCI. |
| | E)COMPLETE REPORT FOR GARAGE DOORS. |
| | F)UPDATED REPORT FOR ENTRY DOORS WITH |
| | SIDELITE. REPORT TO HAVE DADE COUNTY |
| | LOGO AT BOTTOM LEFT OF PAGE. ALSO, |
| | NEED UPDATED LEGIBLE DRAWINGS WITH |
| | RENEWAL STAMP BY DADE COUNTY. |
| | |
| | 11-STORM SHUTTERS: A)MEAN ROOF HEIGHT IS |
| | +/-18'-0" REVISE AS REQUIRED. |
| | B)SEE ENGINEERED DWGS FOR MAXIMUM AND |
| | MINIMUM PANEL SPAN ALLOWED AND REVISE |
| | INSTALLATION SCHEDULE AS REQUIRED. |
| | C)SEE ENGINEERING DWGS FOR ANCHOR TYPE & |
| | SPACING TO BE USED AND REVISE INSTALLA |
| | TION SCHEDULE AS REQUIRED. |
| | D)DWG 1 OF 1 OF ENGINEERED DWGS: REVISE |
| | DESIGN PRESSURES ACCORDING TO THE MEAN |
| | ROOF HEIGHT AND CLEARLY MARK ANCHOR |
| | TYPE AND SPACING. |
| | |
| | 12-ENERGY CALCULATIONS BY EARTH SMART |
| | AND ARCHITECT'S ENERGY CALCS DON'T |
| | MATCH. REVISE AS REQUIRED. |
| | 13-CONTRACTOR INSURANCE IS EXPIRED. |
| | UPDATE AS REQUIRED. |
| | 14-SHEET GN AND SHEET A-1: UPDATE CONC. |
| | GENERAL NOTE. SEE SEC. 1901 FBC 2001 |
| | AND COMMENTS ON DRAWINGS. |
| | 15-SPECIFY SAFETY GLASS FOR GLASS BLOCK |
| | AT TUB IF FACE THICKNESS IS LESS THAN |
| | 0.25". SEC. 2405.2 FBC 2001. |
| | 16-MEAN ROOF HEIGHT IS TAKEN FROM FINISH |
| | GRADE, NOT FROM FINISH FLOOR. REVISE |
| | ELEVATIONS AS REQUIRED. |
| | 17-SHEET A-5A AND A-5B: |
| | A)UPDATE DETAIL 1/A-5A. HUGHES IS OUT |
| | OF BUSINESS. |
| | B)CLARIFY CONSTRUCTION AT ENTRY TOWER. |
| | IS THERE A LEDGER SUPPORTING TRUSSES |
| | OR ARE TRUSSES RESTING ON THE WALL?. |
| | DETAIL 3/A8 DOESN'T SHOW IT. |
| | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| | C)THERE ARE SOME CONNECTORS MISSING. SEE |
| | PLANS FOR COMMENTS. |
| | D)REVISE ROOF NAILING DIAPHRAGM. ZONE |
| | 3 TO BE INCLUDED. SEE FIGURE 1606.2(C) |
| | |
| | 18-OWES $104.10 FOR UPDATED VALUATION |
| | AND RADON FEES. |