Plan Review Notes
Plan Review Notes For Permit 03050057
Permit Number 03050057
Review Stop E
Sequence Number 3
Notes
Date Text
2005-02-25 00:00:00******NOTES REDLINED/ PROVISO *********
  
  
  
 PURSUANT TO DECISION BY THE AHJ AND
 BUILDING OFFICAL, CIRCUITING FOR "ALL"
 BEDROOOM "OUTLETS ARE TO BE BROUGHT UP
 TO THE 2002 NEC FOR ARC FAULT
 PROTECTION. PER 210.12
  
 PLANS WILL BE REQUIRED TO BE REVISED IN
 ORDER TO ADD AF PROTECTION.
  
 PLEASE SEE ALL OUTLETS: INCLUSIVE OF
 SD'S , LTS, RECEPTS, FANS ETC.
  
 PLEASE REVISE AND SUBMIT FOR REVIEW
 BEFORE ROUGH ELECTRICAL INSPECTION.
 IF THERE ARE ANY QUESTIONS, PLEASE DO
 NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]