Plan Review Notes
Plan Review Notes For Permit 03050057
Permit Number 03050057
Review Stop P
Sequence Number 2
Notes
Date Text
2005-03-05 00:00:00PASSED/PROVISO
  
  
 PLUMBING APPROVAL ONLY.SEPARATE PERMIT
 REQUIRED FOR GAS. MORE INFORMATION WILL
 BE REQUIRED WHEN APPLYING FOR PERMIT.
 - SPECIFICATION SHEET FOR ADA ACCESSIBLE
 SLIDING DOOR HARDWARE FOR DOOR AT ROOM
 #104A REQUIRED AT TIME OF FINAL INSPECT-
 ION. -
  
  
 PLUMBING PROVISO
  
 SHT P7-3.01 WATER HAMMER ARRESTORS ARE
 REQUIRED ON THE WATER SUPPLY PIPING FOR
 THE WASH MACHINES. SECTION 604.9 LOCATED
 PER PDI-WH 201 NEAR THE FIXTURES.
  
 SHT P7-3.01 FULL OPEN VALVES ARE
 REQUIRED ON THE TOP OF ALL WATER
 DOWN-FEED PIPES PER SECTION 606.1(4)
  
 SHT P7-3.02 CLEANOUTS ARE REQUIRED AT
 THE WASH MACHINES MINIMUM 4' ABOVE THE
 FLOOR FOR ACCESS. SECTION 708.10