Plan Review Notes
Plan Review Notes For Permit 03050054
Permit Number 03050054
Review Stop E
Sequence Number 2
Notes
Date Text
2003-10-03 00:00:00************** UNSAT ****************
  
 1)NOTE: RESPONSE LETTER MENTIONS THE
 REASON FOR SIZE OF CONDUCTORS ARE DUE TO
 THE DISTANCE OF 260' AWAY. PLEASE SEE
 THAT THE MIN SIZE WOULD BE 3/0'S. THE
 SIZE HAS BEEN INCREASED TO (TWO) SETS
 OF 250MCM. IT IS UNDERSTANDABLE TO
 INCREASE TO 250MCM DUE TO VOLTAGE DROP,
 HOWEVER TWO-SETS OF 250MCM IS NOT CLEAR.
 PLEASE SEE NOTE FROMLAST REVIEW.
 IF INDEED 2-SETS OF 250MCM IS INSTALLED,
 PLEASE PROVIDE A NOTE ON PLAN ON HOW
 THESE WILL TERMINATE INTO A SINGLE 200A
 BRKR THAT WILL NOT ACCOMADATE 2-SETS
 OF 250MCM.
  
 2)NOTE: PLEASE SEE BLDG PLAN REVIEW
 NOTES. PLEASE CORRELATE PLANS/PAPERWORK
 FOR COTTAGES.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]