| Plan Review Notes For Permit 03050054 |
| Permit Number |
03050054 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-10-03 00:00:00 | ************** UNSAT **************** | | | | | | 1)NOTE: RESPONSE LETTER MENTIONS THE | | | REASON FOR SIZE OF CONDUCTORS ARE DUE TO | | | THE DISTANCE OF 260' AWAY. PLEASE SEE | | | THAT THE MIN SIZE WOULD BE 3/0'S. THE | | | SIZE HAS BEEN INCREASED TO (TWO) SETS | | | OF 250MCM. IT IS UNDERSTANDABLE TO | | | INCREASE TO 250MCM DUE TO VOLTAGE DROP, | | | HOWEVER TWO-SETS OF 250MCM IS NOT CLEAR. | | | PLEASE SEE NOTE FROMLAST REVIEW. | | | IF INDEED 2-SETS OF 250MCM IS INSTALLED, | | | PLEASE PROVIDE A NOTE ON PLAN ON HOW | | | THESE WILL TERMINATE INTO A SINGLE 200A | | | BRKR THAT WILL NOT ACCOMADATE 2-SETS | | | OF 250MCM. | | | | | | 2)NOTE: PLEASE SEE BLDG PLAN REVIEW | | | NOTES. PLEASE CORRELATE PLANS/PAPERWORK | | | FOR COTTAGES. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|