| Plan Review Notes For Permit 03050052 |
| Permit Number |
03050052 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-10-03 00:00:00 | *********** UNSAT *************** | | | | | | 1)NOTE: RESPONSE LETTER MENTIONS THE | | | REASON FOR SIZE OF CONDUCTORS ARE DUE | | | TO THE DISTANCE OF 260' AWAY. PLEASE SEE | | | THAT THE MIN SIZE WOULD BE 3/0'S. THE | | | SIZE HAS BEEN INCREASED TO (TWO SETS) | | | OF 250MCM. IT IS UNDERSTANDABLE TO | | | INCREASE TO 250MCM, BUT 2-SETS OF 250MCM | | | (510A'S) IS NOT CLEAR. | | | PLEASE SEE NOTE FROM LAST REVIEW. | | | IF INDEED 2-SETS OF 250MCM IS GOING TO | | | BE USED, PLEASE PROVIDE A NOTE ON PLAN | | | ON HOW THESE WILL TERMINATE INTO A | | | SINGLE 200A BRKR THAT WILL NOT | | | ACCOMADATE 2-SETS OF 250MCM. | | | | | | 2)NOTE: PLEASE SEE BLDG PLAN REVIEW | | | NOTES. PLEASE CORRELATE PLANS/COTTAGES/ | | | PERMIT APPLICATIONS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | DPALMER@WPB. |
|