2003-10-03 00:00:00*********** UNSAT ***************
  
 1)NOTE: RESPONSE LETTER MENTIONS THE
 REASON FOR SIZE OF CONDUCTORS ARE DUE
 TO THE DISTANCE OF 260' AWAY. PLEASE SEE
 THAT THE MIN SIZE WOULD BE 3/0'S. THE
 SIZE HAS BEEN INCREASED TO (TWO SETS)
 OF 250MCM. IT IS UNDERSTANDABLE TO
 INCREASE TO 250MCM, BUT 2-SETS OF 250MCM
 (510A'S) IS NOT CLEAR.
 PLEASE SEE NOTE FROM LAST REVIEW.
 IF INDEED 2-SETS OF 250MCM IS GOING TO
 BE USED, PLEASE PROVIDE A NOTE ON PLAN
 ON HOW THESE WILL TERMINATE INTO A
 SINGLE 200A BRKR THAT WILL NOT
 ACCOMADATE 2-SETS OF 250MCM.
  
 2)NOTE: PLEASE SEE BLDG PLAN REVIEW
 NOTES. PLEASE CORRELATE PLANS/COTTAGES/
 PERMIT APPLICATIONS.
  