Plan Review Notes
Plan Review Notes For Permit 03050051
Permit Number 03050051
Review Stop E
Sequence Number 7
Notes
Date Text
2006-06-20 00:00:00*** REV FOR COTTAGE #7,
  
 PLANS REDLINED:
 PLEASE SEE THERE IS CIRCUITING ON PLANS
 WHICH REFLECT APANEL 6L/AAND 7L/A?
 PLEASE SEE THAT THE PANEL SCHEDULE
 INDICATES 6L/A WHEN IT SHOULD BE 7L/A.
 PLEASE SEE THAT PLANS ARE ALSO LABELED
 WITH COTTAGES 8 AND 9.
 THE ABOVE WAS REDLINED AND WHEN
 REVISIONS ARE SUBMITTED PLANS SHALL BE
 CORRECTED AND SPECIFIC TO JOB, PERMIT
 NUMBER, LOCATION OF BUILDING AND COTTAGE
 #.
 THIS REVISION WAS FOR POWER PLANS AND
 PANEL SCHEDULE REV'S ONLY , NO LIGHTING
 SUBMITTED FOR REVISIONS.
 ALL CIRCUITING PER 2002 NEC WAS REDLINED
 ON PLANS.
 ANY CHANGES SHALL BE SUBMITTED FOR
 REVIEW BEFORE ROUGH ELECTRICAL
 INSPECTION.