| Plan Review Notes For Permit 03050051 |
| Permit Number |
03050051 |
|
| Review Stop |
E |
| Sequence Number |
7 |
|
| Notes |
| Date |
Text |
| 2006-06-20 00:00:00 | *** REV FOR COTTAGE #7, | | | | | | PLANS REDLINED: | | | PLEASE SEE THERE IS CIRCUITING ON PLANS | | | WHICH REFLECT APANEL 6L/AAND 7L/A? | | | PLEASE SEE THAT THE PANEL SCHEDULE | | | INDICATES 6L/A WHEN IT SHOULD BE 7L/A. | | | PLEASE SEE THAT PLANS ARE ALSO LABELED | | | WITH COTTAGES 8 AND 9. | | | THE ABOVE WAS REDLINED AND WHEN | | | REVISIONS ARE SUBMITTED PLANS SHALL BE | | | CORRECTED AND SPECIFIC TO JOB, PERMIT | | | NUMBER, LOCATION OF BUILDING AND COTTAGE | | | #. | | | THIS REVISION WAS FOR POWER PLANS AND | | | PANEL SCHEDULE REV'S ONLY , NO LIGHTING | | | SUBMITTED FOR REVISIONS. | | | ALL CIRCUITING PER 2002 NEC WAS REDLINED | | | ON PLANS. | | | ANY CHANGES SHALL BE SUBMITTED FOR | | | REVIEW BEFORE ROUGH ELECTRICAL | | | INSPECTION. |
|