Plan Review Notes
Plan Review Notes For Permit 03050051
Permit Number 03050051
Review Stop E
Sequence Number 2
Notes
Date Text
2003-10-03 00:00:00************ UNSAT *****************
  
 1)NOTE: RESPONSE LETTER MENTIONS THE
 SIZE OF CONDUCTORS ARE DUE TO THE
 DISTANCE OF 260' AWAY. PLEASE SEE THAT
 MIN SIZE WOULD BE 3/0'S AND SIZE HAS
 BEEN INCREASED TO (TWO SETS) OF 250 MCM'
 S. IT IS UNDERSTANDABLE TO INCREASE TO
 250 MCM, BUT 2-SETS IS NOT CLEAR? PLEASE
 SEE NOTE FROM LAST REVIEW. IF INDEED
 2SETS OF 250MCM IS GOING TO BE USED,
 PLEASE PROVIDE A NOTE ON HOW THESE WILL
 TERMINATE INTO A SINGLE 200A BRKR THAT
 WILL NOT ACCOMADATE TWO SETS OF 250MCM.
  
 2)NOTE: PLEASE SEE BLDG REVIEW NOTES FOR
 CORRELATION OF PLANS/COTTAGES AND ALL
 PAPERWORK
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  