| Plan Review Notes For Permit 03050050 |
| Permit Number |
03050050 |
|
| Review Stop |
E |
| Sequence Number |
6 |
|
| Notes |
| Date |
Text |
| 2006-05-18 00:00:00 | ** UNSAT ** | | | | | | 1) NOTE: PLEASE VERIFY CIRCUITING ON | | | PLANS AND CORRELATE WITH THE SUBMITTED | | | PANEL SCHEDULE(S). | | | PLEASE SEE SOME CIRCUITING AS SHOWN ON | | | PLANS FOR RECEPTS DO NOT CORRELATE WITH | | | AFCI BREAKERS IN PANELS. | | | 210.12B | | | | | | 2) NOTE: PLEASE VERIFY SD'S AS | | | CIRCUITING IS NOT SHOWN FOR THESE. IF | | | THESE ARE LV AND FED FROM A FA SYSTEM, | | | PLEASE NOTE ON PLANS. | | | IF NOT PLEASE CIRCUIT AND AFCI. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|