2006-06-11 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6652
 E-MAIL: [email protected]
  
 ARCHITECTURAL/STRUCTURAL REVISION FOR
 SHEETS A6-2.1, A6-4.2, A6-5.2, A6-6.1,
 A6-11.1, S-7.02 AND S-7.03
  
 1) THE ARCHITECTURAL SHEETS HAVE BEEN
 SEPARATED AND STAMPED SEPARATELY BECAUSE
 THE SCHEDULE ON STRUCTURAL SHEET S-7.02
 HAS AN INCORRECT TRUSS CONNECTOR/HANGER
 REFERENCE.THE CAPACITIES STATED ON THE
 PLAN ARE FOR A HHDO212-2 HANGER BUT THE
 PLAN REFERS TO HDO212-2 WHICH HAS LOWER
 CAPACITIES.AMEND THE SCHEDULE ON SHEET
 S-7.02 AND RESUBMIT BOTH STRUCTURAL
 SHEETS.THE ARCHITECTURAL SHEETS ARE OK
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 TELEPHONE: (561) 805 6652ROBERT BROWN
 E-MAIL: [email protected]