2006-04-24 00:00:00******* UNSAT ************
  
 1) NOTE: PLEASE SEE NOTES BELOW AS THE
 "PROVISO" WHICH WAS SET UP IN ORDER TO
 ISSUETHE BUILDING PERMIT HAS NOT BEEN
 ADDRESSED TO DATE.
 THIS WAS A CONDITION AS PERMITS HAD
 EXPIRED AND EXTENSION WAS GRANTED BY THE
 AHJ AND BUILDING OFFICAL THAT ALL
 ELECTRICAL BE BROUGHT UP TO THE 2002
 NEC. THIS WAS REQUIRED TO BE DONE BEFORE
 ROUGH ELECTRICAL INSPECTION AND TO DATE
 PLANS MEETING THIS HAVE NOT BEEN
 SUBMITTED.
 PLEASE COMPLETE ROOMAND AREA
 DESIGNATIONS ON PLANS, AND CORRELATE ALL
 CIRCUTING TO PANEL SCHEDULES TO BE
 SUBMITTED.
 PLEASE SEE NOTES.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 DPALMER2WPB.ORG.
  
  
  
  
  
  
 ******NOTES REDLINED/ PROVISO *********
  
  
  
 PURSUANT TO DECISION BY THE AHJ AND
 BUILDING OFFICAL, CIRCUITING FOR "ALL"
 BEDROOOM "OUTLETS ARE TO BE BROUGHT UP
 TO THE 2002 NEC FOR ARC FAULT
 PROTECTION. PER 210.12
  
 PLANS WILL BE REQUIRED TO BE REVISED IN
 ORDER TO ADD AF PROTECTION.
  
 PLEASE SEE ALL OUTLETS: INCLUSIVE OF
 SD'S , LTS, RECEPTS, FANS ETC.
  
 PLEASE REVISE AND SUBMIT FOR REVIEW
 BEFORE ROUGH ELECTRICAL INSPECTION.
 IF THERE ARE ANY QUESTIONS, PLEASE DO
 NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]