| Date |
Text |
| 2006-04-24 00:00:00 | ******* UNSAT ************ |
| | |
| | 1) NOTE: PLEASE SEE NOTES BELOW AS THE |
| | "PROVISO" WHICH WAS SET UP IN ORDER TO |
| | ISSUETHE BUILDING PERMIT HAS NOT BEEN |
| | ADDRESSED TO DATE. |
| | THIS WAS A CONDITION AS PERMITS HAD |
| | EXPIRED AND EXTENSION WAS GRANTED BY THE |
| | AHJ AND BUILDING OFFICAL THAT ALL |
| | ELECTRICAL BE BROUGHT UP TO THE 2002 |
| | NEC. THIS WAS REQUIRED TO BE DONE BEFORE |
| | ROUGH ELECTRICAL INSPECTION AND TO DATE |
| | PLANS MEETING THIS HAVE NOT BEEN |
| | SUBMITTED. |
| | PLEASE COMPLETE ROOMAND AREA |
| | DESIGNATIONS ON PLANS, AND CORRELATE ALL |
| | CIRCUTING TO PANEL SCHEDULES TO BE |
| | SUBMITTED. |
| | PLEASE SEE NOTES. |
| | |
| | IF THERE ARE ANY QUESTIONS, PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | DPALMER2WPB.ORG. |
| | |
| | |
| | |
| | |
| | |
| | |
| | ******NOTES REDLINED/ PROVISO ********* |
| | |
| | |
| | |
| | PURSUANT TO DECISION BY THE AHJ AND |
| | BUILDING OFFICAL, CIRCUITING FOR "ALL" |
| | BEDROOOM "OUTLETS ARE TO BE BROUGHT UP |
| | TO THE 2002 NEC FOR ARC FAULT |
| | PROTECTION. PER 210.12 |
| | |
| | PLANS WILL BE REQUIRED TO BE REVISED IN |
| | ORDER TO ADD AF PROTECTION. |
| | |
| | PLEASE SEE ALL OUTLETS: INCLUSIVE OF |
| | SD'S , LTS, RECEPTS, FANS ETC. |
| | |
| | PLEASE REVISE AND SUBMIT FOR REVIEW |
| | BEFORE ROUGH ELECTRICAL INSPECTION. |
| | IF THERE ARE ANY QUESTIONS, PLEASE DO |
| | NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |