Plan Review Notes
Plan Review Notes For Permit 03050047
Permit Number 03050047
Review Stop E
Sequence Number 1
Notes
Date Text
2003-05-08 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE MAKE THE FOLOWING CHANGES TO THE
 PLAN FOR CODE COMPLIANCE AND RESUBMIT
 FOR REVIEW.
  
 1} THE 2 POLE 55AMP BREAKER ON THE PANEL
 SCHEDULE FOR AHU #1 IS INCORRECT PER
 240-6,MUST BE A 60 AMP.
  
 2} THERE ARE EXCESSIVE LOADS IN THE
 CALC'S FOR THE GAS APPLIANCES.PLEASE
 CHANGE TO INDICATE THE CORRECT LOADS
 AND VERIFY IF THEY ARE GAS OR ELECTRIC.
  
 3} THE RECEPTACLE FOR THE WHIRLPOOL MUST
 BE SHOWN AS GFI PER 680.
  
 4} PLEASE NOTE KITCHEN COUNTER-
 SPACE RECEPT SPACING SHALL MEET ART;
 210-52C 1,2,3,4,AND 5.AND BE SHOWN ON
 THE PLAN TO BE GFI PER 210-8(A)(6).
  
 5} SHOW HOW THE LOGGIA EGRESS MEETS
 210-70.
  
 6} PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2',6',12' RULE PER 210-52.
 SEE REDLINED DRAWINGS.
  
 7} THERE IS A SUB PANEL SHOWN IN THE
 GARAGE BUT NO PANEL SCHEDULE FOR
 SAME.PLEASE PROVIDE A PANEL SCHEDULE
 PER 215-5.
  
 8} THERE IS NO FEED SHOWN TO THE SUB
 PANEL FROM THE ELECTRIC PANEL. INDICATE
 HOW IT IS FED
  
 9} THE "POWDER ROOM" MUST HAVE A GFI
 RECEPTACLE TO COMPLY WITH 210-52(D).
  
 10} PLEASE NOTE THAT PLANS ARE TO
 BE SIGNED, DATED AND SEALED BY AN P.E.
 PER FS/FAC 553-79-6A.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/508-6718