| 2003-05-08 00:00:00 | UNSAT |
| | ~~~~~ |
| | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ |
| | PLEASE MAKE THE FOLOWING CHANGES TO THE |
| | PLAN FOR CODE COMPLIANCE AND RESUBMIT |
| | FOR REVIEW. |
| | |
| | 1} THE 2 POLE 55AMP BREAKER ON THE PANEL |
| | SCHEDULE FOR AHU #1 IS INCORRECT PER |
| | 240-6,MUST BE A 60 AMP. |
| | |
| | 2} THERE ARE EXCESSIVE LOADS IN THE |
| | CALC'S FOR THE GAS APPLIANCES.PLEASE |
| | CHANGE TO INDICATE THE CORRECT LOADS |
| | AND VERIFY IF THEY ARE GAS OR ELECTRIC. |
| | |
| | 3} THE RECEPTACLE FOR THE WHIRLPOOL MUST |
| | BE SHOWN AS GFI PER 680. |
| | |
| | 4} PLEASE NOTE KITCHEN COUNTER- |
| | SPACE RECEPT SPACING SHALL MEET ART; |
| | 210-52C 1,2,3,4,AND 5.AND BE SHOWN ON |
| | THE PLAN TO BE GFI PER 210-8(A)(6). |
| | |
| | 5} SHOW HOW THE LOGGIA EGRESS MEETS |
| | 210-70. |
| | |
| | 6} PLEASE SHOW ALL OUTLET SPACING |
| | TO MEET 2',6',12' RULE PER 210-52. |
| | SEE REDLINED DRAWINGS. |
| | |
| | 7} THERE IS A SUB PANEL SHOWN IN THE |
| | GARAGE BUT NO PANEL SCHEDULE FOR |
| | SAME.PLEASE PROVIDE A PANEL SCHEDULE |
| | PER 215-5. |
| | |
| | 8} THERE IS NO FEED SHOWN TO THE SUB |
| | PANEL FROM THE ELECTRIC PANEL. INDICATE |
| | HOW IT IS FED |
| | |
| | 9} THE "POWDER ROOM" MUST HAVE A GFI |
| | RECEPTACLE TO COMPLY WITH 210-52(D). |
| | |
| | 10} PLEASE NOTE THAT PLANS ARE TO |
| | BE SIGNED, DATED AND SEALED BY AN P.E. |
| | PER FS/FAC 553-79-6A. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | 561/508-6718 |