| Notes |
| Date |
Text |
| 2003-05-13 00:00:00 | PROVISO | | | ~~~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE CHECK THE NAMEPLATE RATINGS OF | | | BOTH AIR HANDLERS AND USE THE CORRECT | | | OVERCURRENT PROTECTION FOR SAME. | | | ALSO CORRECT THE WATER HEATER CIRCUIT | | | AND USE CORRECT WIRE AND OCP FOR SAME. | | | HAVE FIELD INSPECTOR VERIFY CORRECTIONS | | | ON ROUGH INSPECTION. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 |
|