| Plan Review Notes For Permit 03050030 |
| Permit Number |
03050030 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-05-08 00:00:00 | DENIED:MECHANICAL PERMIT 03050078 | | | | | | 1.PLAN SHEET A.4.1.1 MECH RM #G30, | | | PARTITION WALL BETWEEN MECH RM & | | | VESTIBULE IS A RATED WALL.PLAN SHEET | | | M.4.3.1 SHOWS 17/12 DUCT PENETRATING | | | THIS RATED PARTITION WITHOUT A FIRE | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|