| 2003-06-05 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 03042704 |
| | ADD: 201 S NARCISSUS AVE |
| | CONT: POOL PEOPLE COMMERCIAL INC |
| | TEL: (954)972-6300 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | ACTION: DENIED |
| | |
| | 1) 424.1 PUBLIC SWIMMING POOLS |
| | DEPARTMEENT OF HEALTH 64E-9 (6) |
| | EFFECTIVE BARRIER- A EFFECTIVE BARRIER |
| | WHICH CONSIST OF A BUILDING PLUS A 42" |
| | MINIMUM FENCE ON THE REMAINING THREE |
| | SIDES OR A FOUR SIDED FENCE. ALL ACCESS |
| | THROUGH THE BARRIER MUST HAVE ONE OR |
| | MORE OF THE SAFETY DEVICES: ALARM,KEY |
| | LOCK OR SELF-LOCKING DOORS OR GATES. |
| | SAFETY COVERS THAT COMPLY WITH THE ASTM- |
| | F 1346 MAY ALSO BE CONSIDERED AS AN |
| | EFFECTIVE BARRIER. |
| | |
| | 13-412.1.ABCD.2.4.2.POOL COVERS REQUIRED |
| | SPAS & HEATED SWIMMING POOLS SHALL BE |
| | EQUIPPED WITH A COVER DESIGNED TO MINI- |
| | MIZE HEAT LOSS. |
| | |
| | LOOK FOR COMMENTS BY THE OTHER PLAN |
| | REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| | ON THE APPLICATION, PLANS, OR ATTACHED |
| | SEPARATELY. WHEN RESUBMITTING PLANS |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| | THE PLANS WHEN RESUBMITTING PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN |
| | BE FOUND, WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | JIM WITMER |
| | BUILDING PLAN REVIEW |
| | TEL: (561)659-8096 X 8412 |
| | FAX: (561)659-8026 |