| 2003-05-14 00:00:00 | UNSAT |
| | ~~~~~ |
| | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ |
| | PLEASE PROVIDE THE FOLLOWING |
| | INFORMATION,MAKE ANY NECESSARY CHANGES |
| | ON THE PLANS AND RESUBMIT FOR REVIEW. |
| | |
| | 1} PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRENT PER 110-9. |
| | |
| | 2} PLEASE SHOW THE GROUNDING ELECTRODE |
| | SYSTEM IN COMPLIANCE WITH 250-50(A,B & |
| | C) |
| | |
| | 3} THE CALCULATION FOR THE A/C SYSTEM ON |
| | THE PANEL SCHEDULE AND THE LOAD CALC'S |
| | DO NOT CORRELATE. |
| | |
| | 4} THE SMALL APPLIANCE CIRCUITS MUST BE |
| | CALCULATED @ 1500 VA.EA PER 220-16(A). |
| | |
| | 5} THERE IS ONLY ONE GENERAL LIGHTING |
| | CIRCUIT ON THE PANEL SCHEDULE.THERE |
| | MUST BE A MINIMUM OF THREE @ 15AMPS. |
| | |
| | 6} PLEASE LIST THE REQ'D BATH(S) |
| | CIRCUIT(S). PER 210-11-C-3 |
| | MUST BE 20A AND #12AWG. |
| | |
| | 7} SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | PER 8-1.4.2,NFPA-72. |
| | |
| | 8} PLEASE LIST THE REQ'D ARC |
| | FAULT PROTECTED CIRCUITS ON PANEL |
| | SCHEDULE OR NOTE ON PLANS FOR BRANCH |
| | CIRCUIT PROTECTION. PER 210-12 |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | 561/805-6718 |