| Plan Review Notes For Permit 03042682 |
| Permit Number |
03042682 |
|
| Review Stop |
B |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2003-08-07 00:00:00 | SUBMITTAL CHECKLIST: | | | 1-DETAIL 12/A6 KEYED FOR FAMILY ROOMAT | | | GABLE END DOESN'T APPLY. NEED TO | | | PROVIDE RAKE BEAM BECAUSE OF VAULTED | | | CEILING AT THIS AREA TO COMPLY WITH | | | SECTION 2117.1.2 FBC 2001. | | | 2-REVISE ANCHOR SPECIFIED ON DETAIL | | | 10/A5. IF USING SIMPSON ANCHORS, THEN, | | | NEED TO SEE THE SIMPSON HIGH WIND- | | | RESISTANT CONSTRUCTION CATALOGUE, | | | WHICH IS THE ONLY ONE REVISED TO | | | COMPLY WITH SECTION 1609.4.3 FBC 2001. | | | **NOTE: ONLY THE ANCHORS HIGHLIGHTED | | | ORANGE ARE THE ONES WHO WERE REVISED | | | TO NO INCLUDE THE STEEL STRESS | | | INCREASE. | | | 3-CONTRACTOR TO PROVIDE ALL INFORMATION | | | REQUESTED ON PROVISO DATED 8-4-03 | | | TO AVOID ANY DELAYS OR CONFLICTS | | | DURING CONSTRUCTION. |
|