| 2003-07-10 00:00:00 | SECOND CHECKLIST: |
| | 1-ENERGY CALCULATIONS WERE NOT REVISED: |
| | A)A/C AREA DOESN'T MATCH A/C AREA SHOWN |
| | ON PLANS. |
| | B)ENERGY CALCULATIONS NEED TO BE DONE |
| | WORST CASE SCENARIO FOR A PARTICULAR |
| | MODEL OR SITE SPECIFIC. ENERGY CALCS. |
| | SUBMITTED ARE NEITHER OF THE ABOVE. |
| | REVISE AS REQUIRED. |
| | C)REVISE UNDER ATTIC AREA TO COMPLY WITH |
| | SEC. 602.1ABC.1.2 CHAPTER 13 FBC 2001. |
| | |
| | 2-PROVIDE SOIL TEST REPORT. |
| | 3-PROVIDE PRODUCT APPROVAL FOR: |
| | A)ROOF TILE. (IT'S SEPARATE PERMIT |
| | BECAUSE SUBCONTRACTOR DIDN'T SIGN THE |
| | APPLICATION, BUT INFORMATION STILL IS |
| | REQUIRED). |
| | B)ENTRY DOORS WITH UPDATED DADE COUNTY |
| | REPORT WITH LOGO AT BOTTOM LEFT OF 1ST |
| | PAGE AND WITH LEGIBLE DRAWINGS WITH |
| | RENEWAL STAMP. |
| | C)GARAGE DOORS WITH LEGIBLE DRAWINGS. |
| | D)SITE SPECIFIC ENGINEERING NEED SITE |
| | SPECIFIC INFORMATION FOR A SPECIFIC |
| | BUILDING. INFORMATION SUBMITTED FOR |
| | THE MULLIONS IS GENERIC. NEED COMPLETE |
| | INFORMATION SPECIFIC TO THIS JOB SITE. |
| | CLEARLY SPECIFY ALL COMPONENTS TO BE |
| | USED IN THIS PROJECT. MULLION SIZE, |
| | ANCHORS, DESIGN PRESSURES ETC. ALSO, |
| | NEED TO INDICATE THE ADDRESS OF THIS |
| | PROJECT. |
| | **ALSO, COMPLETE SITE SPECIFIC FORM AS |
| | DONE FOR THE SITE SPECIFIC ARCHED |
| | WINDOWS. |
| | E)NEED PRODUCT APPROVAL FOR STRUCTURAL |
| | HEADER ABOVE SLIDING GLASS DOORS. SEE |
| | PLANS FOR SIZE SPECIFIED. |
| | F)NEED GLASS PRODUCT APPROVAL WITH |
| | LEGIBLE DRAWINGS. |
| | |
| | 4-REVISE BOLT SIZE SPECIFIED FOR ANCHOR |
| | SHOWN ON DETAIL 10/A5. SEE SIMPSON |
| | CATALOGUE. ALSO: NEED TO USE SIMPSON |
| | CATALOGUE FOR HIGH WIND-RESISTANT |
| | CONSTRUCTION CATALOGUE SINCE IS THE |
| | ONLY ONE BEEN REVISED TO COMPLY WITH |
| | SECTION 1609.4.3 FBC 2001. |
| | 5-REVISE GABLE END CONSTRUCTION AT |
| | FAMILY ROOM AREA TO COMPLY WITH SEC. |
| | 2117.1.2 FBC 2001. |
| | **ALSO, CLARIFY CONSTRUCTION OF GABLE |
| | AT REAR PORCH. DETAILS 2/A5 AND 6/A5 |
| | DON'T APPLY. SEC. 104.2.1.2 CITY |
| | AMENDMENTS TO FBC 2001. |
| | 6-OWES $774.32 FOR WESTERN EXPANSION |
| | FEES AND RADON FEES. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ @ (561)805-6712. |
| | |
| | **NOTE: PLEASE INSERT ANY REVISED DWGS |
| | INTO THE SETS AND DISCARD OLD DRAWINGS |