| 2003-06-13 00:00:00 | ****************** UNSAT *********** |
| | |
| | PLEASE NOTE, NOW A RISER DIAGRAM AND |
| | LOAD CALCULATIONS HAVE BEEN SUBMITTED |
| | FOR REVIEW. PLEASE SEE THE FOLLOWING |
| | COMMENTS. |
| | |
| | 1)NOTE; PLEASE SEE RISER, MISSING |
| | CONDUCTORS FROM 200A MAIN PANEL TO NEW |
| | 125A SUB-PANEL? AS PREVIOUSLY NOTED. |
| | 215-5 |
| | 2)NOTE; PLEASE PROVIDE OCP SIZE AT MAIN |
| | PANEL FOR SUB-FEED.215-5 |
| | |
| | 3)NOTE: PLEASE SEE LOAD CALCULATIONS. |
| | LOAD IS AT 285A. PLANS NOTE THAT SERVICE |
| | IS 400A`S?? PLEASE SEE RISER MAIN PANEL |
| | IS SHOWN AS 200A`S?? |
| | PLEASE INCREASE SERVICE,TO INCLUDE NEW |
| | CONDUIT/WIRE ETC |
| | |
| | 4)NOTE: PLEASE SEE 225-31 FOR MISSING |
| | MEANS OF DISC AT DETACHED STRUCTURE. |
| | |
| | 5)NOTE: PLEASE SEE MISSING GROUNDING |
| | ELECTRODE SYSTEM AT DETACHED BLDG AND |
| | EQUIPMENT GROUNDING CONDUCTOR FROM MAIN |
| | PANEL TO NEW SUB PANEL.250-30 |
| | PLEASE INCLUDE COLD WATER LINE. |
| | |
| | 6)NOTE: PLEASE CLARIFY SERVICE RISER, |
| | NOTES TO EXISTING PANEL IN GARAGE? |
| | IF 200A PANEL SHOWN ON RISER IS ALL NEW? |
| | IS PANEL IN GARAGE BEING INCLUDED IN |
| | ENTIRE SERVICE? PLEASE SEE 230-72 FOR |
| | GROUPING OF MAINS. ONE MAIN CAN NOT BE |
| | OUTSIDE AND OTHER INSIDE? |
| | |
| | 7)NOTE: PLEASE SUBMIT AIC RATING(S) FOR |
| | ALL NEW ELECTRICAL SERVICE EQUIPMENT |
| | BEING INSTALLED. MAINS/PANELS/BRKRS ALL |
| | MUST BE RATED FOR THE AVAILABLE FAULT |
| | CURRENT. 110-9 |
| | |
| | PLEASE NOTE, DUE TO SERVICE NOT BEING |
| | COMPLETE AT THIS TIME, A COMPLETE REVIEW |
| | CAN NOT BE DONE. |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |