Plan Review Notes
Plan Review Notes For Permit 03042197
Permit Number 03042197
Review Stop E
Sequence Number 2
Notes
Date Text
2003-06-13 00:00:00****************** UNSAT ***********
  
 PLEASE NOTE, NOW A RISER DIAGRAM AND
 LOAD CALCULATIONS HAVE BEEN SUBMITTED
 FOR REVIEW. PLEASE SEE THE FOLLOWING
 COMMENTS.
  
 1)NOTE; PLEASE SEE RISER, MISSING
 CONDUCTORS FROM 200A MAIN PANEL TO NEW
 125A SUB-PANEL? AS PREVIOUSLY NOTED.
 215-5
 2)NOTE; PLEASE PROVIDE OCP SIZE AT MAIN
 PANEL FOR SUB-FEED.215-5
  
 3)NOTE: PLEASE SEE LOAD CALCULATIONS.
 LOAD IS AT 285A. PLANS NOTE THAT SERVICE
 IS 400A`S?? PLEASE SEE RISER MAIN PANEL
 IS SHOWN AS 200A`S??
 PLEASE INCREASE SERVICE,TO INCLUDE NEW
 CONDUIT/WIRE ETC
  
 4)NOTE: PLEASE SEE 225-31 FOR MISSING
 MEANS OF DISC AT DETACHED STRUCTURE.
  
 5)NOTE: PLEASE SEE MISSING GROUNDING
 ELECTRODE SYSTEM AT DETACHED BLDG AND
 EQUIPMENT GROUNDING CONDUCTOR FROM MAIN
 PANEL TO NEW SUB PANEL.250-30
 PLEASE INCLUDE COLD WATER LINE.
  
 6)NOTE: PLEASE CLARIFY SERVICE RISER,
 NOTES TO EXISTING PANEL IN GARAGE?
 IF 200A PANEL SHOWN ON RISER IS ALL NEW?
 IS PANEL IN GARAGE BEING INCLUDED IN
 ENTIRE SERVICE? PLEASE SEE 230-72 FOR
 GROUPING OF MAINS. ONE MAIN CAN NOT BE
 OUTSIDE AND OTHER INSIDE?
  
 7)NOTE: PLEASE SUBMIT AIC RATING(S) FOR
 ALL NEW ELECTRICAL SERVICE EQUIPMENT
 BEING INSTALLED. MAINS/PANELS/BRKRS ALL
 MUST BE RATED FOR THE AVAILABLE FAULT
 CURRENT. 110-9
  
 PLEASE NOTE, DUE TO SERVICE NOT BEING
 COMPLETE AT THIS TIME, A COMPLETE REVIEW
 CAN NOT BE DONE.
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  