2003-06-27 00:00:00******CORRECTIONS******
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)THE NAILING FOR THE ROOF SHEATHING
 DOES NOT COMPLY WITH CITY OF WEST PALM
 BEACH AMENDMENTS TO THE FBC, TABLE
 2306.1.
  
 2.)WHEN RESUBMITTING, SUBMIT THE
 OLD SHEETS, MARKED.
  
 3.)SHOW THE FIRESTOP REQUIRED ON THE
 BLOCK WALL DETAIL FBC 705.3.
  
 4.)THE BUILDING SECTION REFERS TO
 "WIRE LATH" ON THE BLOCK WALL.CLARIFY.
  
 5.)ADDITIONAL FEES REQUIRED.
  
 6.)THE SOILS REPORT PROVIDED WAS FOR
 THE POOL.A SOILS INVESTIGATION REPORT
 IS REQUIRED FOR THE STRUCTURE.
  
 7.)SIGN THE OWNER/AGENT LINE OF THE
 ENERGY CALCS.
  
 8.)THE BUILDING SECTION (3-3) SHOWS A
 2' FOOTER WIDTH, THE WALL SECTION SHOWS
 A 3' WIDTH (2-4).