Plan Review Notes
Plan Review Notes For Permit 03042197
Permit Number 03042197
Review Stop B
Sequence Number 1
Notes
Date Text
2003-05-21 00:00:00*******CORRECTIONS********
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE
 A PERMIT CAN BE ISSUED.
  
 2.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE PERMIT
 APPLICATION.233-5025.
  
 3.)SEPARATE PERMITS REQUIRED.
  
 4.)THIS LOT IS IN A FLOOD ZONE.THE
 FINISHED FLOOR ELEVATION MUST BE 6"
 ABOVE BASE FLOOD ELEVATION OF 7';CITY OF
 WEST PALM BEACH MUNICIPAL CODE 94-546.
  
 5.)ENERGY CALCS REQUIRED FBC13-101.2.
  
 6.)PROVIDE A SOILS INVESTIGATION
 REPORT.
  
 7.)NOTE ON THE RETAINING WALL DETAIL
 THAT THE FOOTER IS NOT TO ENCROACH UPON
 THE PROPERTY LINE.
  
 8.)THE STEEL REINFORCEMENT IS NOT
 SHOWN ON THE TYPICAL BEAM DIAGRAM, END
 BEAM ELEVATOIN, OR BUILDING SECTION.
  
 9.)THE LANGUAGE FOR WINDOW BUCK, 1X3,
 MUST COMPLY WITH FBC 1707.4.4.2.
  
 10.)THE NAILING FOR THE T&G CONFLICTS;
 ROOF FRAMING PLAN (16D) AND BUILDING
 SECTION (20D).
  
 11.)ARE THE BLOCK WALLS TO HAVE
 DRYWALL AND INSULATION?IF THEY ARE,
 SHOW ON THE BUILDING SECTION.
  
 12.)FIRESTOPPING REQUIRED, FBC 705.3.
  
 13.)THE SINGLE HUNG WINDOW APPEARS TO
 BE IN A HAZARDOUS LOCATION FBC 2405.2.
  
 14.)PROVIDE A HURRICANE ANCHOR
 SCHEDULE (SEE ATTACHED).
  
 15.)PROVIDE AREA CALCULATIONS.
  
 16.)THE DESIGN PRESSURE FOR THE 6068
 AND 8068 SLIDING GLASS DOORS EXCEED THE
 LOADS ON THE PRODUCT APPROVAL.THE
 1068 SLIDING GLASS DOOR IS NOT ON THE
 PRODUCT APPROVAL.
  
 17.)PROVIDE PRODUCT APPROVALS FOR:
 SLIDING GLASS DOORS (CHECK PRESSURES)
 SINGLE HUNG WINDOW
 2668 DOOR
 BARREL TILE ROOF